Assessment Year | 2023 |
---|---|
Principal Product | Industrial joystick controllers |
NAICS | 335314: Relay and Industrial Control Manufacturing |
SIC | 3625: Relays and Industrial Controls |
Sales Range | $10 M to 50M |
# of Employees | 200 |
Plant Area |
72,000
ft2
|
Annual Production | 133,000
pieces
|
Production Hrs. Annual | 2,000
hrs
|
Location (State) | Connecticut |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $114,925 | 858,480 |
kWh
|
$0.13 |
Electricity Demand | $56,119 | 4,300 |
kW-mo/yr
|
$13.05 |
Electricity Fees | $(-5,269.4) | - |
|
- |
Natural Gas | $26,188 | 1,517 |
MMBtu
|
$17.26 |
TOTAL YEARLY COSTS | $191,962 | |||
RECOMMENDED SAVINGS* | $123,487 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $15,163 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.3192: Use fossil fuel powered generator during peak demand periods | $2,520 | - |
$164
1,224
kWh
|
$355
-
kW-mo/yr
|
$2,320 |
$(-318.8)
-
MMBtu
|
- | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,636 | $11,635 |
$5,258
39,268
kWh
|
$3,075
-
kW-mo/yr
|
- | - | $156 | $147 | |
03 | 2.7124: Make a practice of turning off lights when not needed | $375 | - |
$112
838
kWh
|
$262
-
kW-mo/yr
|
- | - | - | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $795 | $600 |
$542
4,042
kWh
|
$253
-
kW-mo/yr
|
- | - | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,621 | $1,600 |
$1,105
8,250
kWh
|
$517
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.9114: Use solar heat to make electricty | $70,539 | $385,242 |
$78,131
583,501
kWh
|
- | - | - | $(-7,592.0) | - | |
07 | 2.7232: Replace existing hvac unit with high efficiency model | $6,153 | $34,274 |
$(-2,602.7)
(-19,438)
kWh
|
$(-347.5)
-
kW-mo/yr
|
- |
$9,103
-
MMBtu
|
- | - | |
08 | 2.7261: Install timers and/or thermostats | $1,986 | $3,066 |
$180
1,348
kWh
|
- | - |
$1,805
-
MMBtu
|
- | - | |
09 | 2.4322: Use or replace with energy efficient substitutes | $9,865 | $22,297 |
$8,704
65,000
kWh
|
$1,162
-
kW-mo/yr
|
- | - | - | - | |
10 | 2.2136: Install / repair insulation on steam lines | $207 | $733 | - | - | - |
$207
-
MMBtu
|
- | - | |
11 | 2.2511: Insulate bare equipment | $429 | $1,916 |
$429
3,203
kWh
|
- | - | - | - | - | |
12 | 2.7234: Use heat pump for space conditioning | $20,361 | $73,450 |
$(-7,415.4)
(-55,380)
kWh
|
$1,585
-
kW-mo/yr
|
- |
$26,191
-
MMBtu
|
- | - | |
TOTAL RECOMMENDED | $123,487 | $534,813 |
$84,607
631,856
kWh
|
$6,862
-
kW-mo/yr
|
$2,320 |
$36,987
-
MMBtu
|
$(-7,435.8) | $147 | ||
TOTAL IMPLEMENTED | $15,163 | $45,909 |
$2,767
20,668
kWh
|
$2,990
-
kW-mo/yr
|
- |
$9,103
-
MMBtu
|
$156 | $147 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs