Assessment Year | 2011 |
---|---|
Principal Product | Industrial Inorganic Chemicals |
NAICS | 325180: Other Basic Inorganic Chemical Manufacturing |
SIC | 2819: Industrial Inorganic Chemicals, Not Elsewhere Classified |
Sales Range | $1 M to 5M |
# of Employees | 22 |
Plant Area |
26,000
ft2
|
Annual Production | 1,200,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $124,391 | 1,882,586 |
kWh
|
$0.066 |
Electricity Fees | $29,826 | - |
|
- |
LPG | $2,390 | 116 |
MMBtu
|
$20.55 |
Fuel Oil #1 | $137,206 | 7,525 |
MMBtu
|
$18.23 |
Other Energy | $574,458 | 15,688 |
MMBtu
|
$36.62 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $395,209 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $8,080 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | LPG Savings | Fuel Oil #1 Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.1221: Replace obsolete burners with more efficient ones | $361,004 | $66,433 | - | - | - | $361,004 | |
02 | 2.4133: Use most efficient type of electric motors | $4,810 | $17,030 |
$4,810
60,678
kWh
|
- | - | - | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,140 | $2,925 |
$2,140
22,421
kWh
|
- | - | - | |
04 | 2.7231: Use radiant heater for spot heating | $871 | $1,836 | - |
$871
-
MMBtu
|
- | - | |
05 | 2.7261: Install timers and/or thermostats | $1,130 | $397 |
$1,130
11,840
kWh
|
- | - | - | |
06 | 2.2511: Insulate bare equipment | $6,592 | $499 | - | - |
$6,592
-
MMBtu
|
- | |
07 | 2.2427: Use waste heat from hot flue gases to preheat incoming fluids | $18,662 | $50,000 | - | - |
$18,662
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $395,209 | $139,120 |
$8,080
94,939
kWh
|
$871
-
MMBtu
|
$25,254
-
MMBtu
|
$361,004 | ||
TOTAL IMPLEMENTED | $8,080 | $20,352 |
$8,080
94,939
kWh
|
- | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | LPG Savings | Fuel Oil #1 Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs