Assessment Year | 2010 |
---|---|
Principal Product | Automotive Glass |
NAICS | 811122: Automotive Glass Replacement Shops |
SIC | 7536: Automotive Glass Replacement Shops |
Sales Range | $50 M to 100M |
# of Employees | 149 |
Plant Area |
83,840
ft2
|
Annual Production | 2,300,000
pieces
|
Production Hrs. Annual | 4,768
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $281,575 | 3,873,823 |
kWh
|
$0.073 |
Electricity Fees | $311,581 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $39,044 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $2,695 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $24,940 | $18,577 |
$24,940
343,089
kWh
|
|
02 | 2.7135: Install occupancy sensors | $190 | $129 |
$190
2,620
kWh
|
|
03 | 2.7135: Install occupancy sensors | $120 | $129 |
$120
1,650
kWh
|
|
04 | 2.7134: Use photocell controls | $367 | $1,000 |
$367
5,046
kWh
|
|
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,872 | $640 |
$3,872
53,269
kWh
|
|
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,018 | $1,500 |
$2,018
27,764
kWh
|
|
07 | 2.7447: Install vinyl strip / high speed / air curtain doors | $5,858 | $8,376 |
$5,858
80,582
kWh
|
|
08 | 2.7425: Clean or color roof to reduce solar load | $1,679 | $5,534 |
$1,679
23,100
kWh
|
|
TOTAL RECOMMENDED | $39,044 | $35,885 |
$39,044
537,120
kWh
|
||
TOTAL IMPLEMENTED | $2,695 | $2,758 |
$2,695
37,080
kWh
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings |