Assessment Year | 2025 |
---|---|
Principal Product | Palletizing machines and service parts |
NAICS | 333993: Packaging Machinery Manufacturing |
SIC | 3565: Packaging Machinery |
Sales Range | $10 M to 50M |
# of Employees | 108 |
Plant Area |
165,000
ft2
|
Annual Production | 25
units
|
Production Hrs. Annual | 2,500
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $225,701 | 2,221,800 |
kWh
|
$0.10 |
Electricity Demand | $37,444 | 6,603 |
kW-mo/yr
|
$5.67 |
Electricity Fees | $10,174 | - |
|
- |
Natural Gas | $45,109 | 31,602 |
MMBtu
|
$1.43 |
TOTAL YEARLY COSTS | $318,428 | |||
RECOMMENDED SAVINGS* | $13,429 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.4221: Install compressor air intakes in coolest locations | $9,191 | $8,397 |
$8,849
87,095
kWh
|
- | $342 | |
02 | 2.3212: Optimize plant power factor | $2,328 | $1,262 | - | - | $2,328 | |
03 | 2.7134: Use photocell controls | $906 | $2,976 |
$872
8,580
kWh
|
- | $34 | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $795 | $250 |
$581
5,717
kWh
|
$184
-
kW-mo/yr
|
$30 | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $209 | $500 |
$150
1,475
kWh
|
$51
-
kW-mo/yr
|
$8 | |
TOTAL RECOMMENDED | $13,429 | $13,385 |
$10,452
102,867
kWh
|
$235
-
kW-mo/yr
|
$2,742 | ||
TOTAL IMPLEMENTED | - | - | - | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs