Assessment Year | 2024 |
---|---|
Principal Product | Automotive Parts |
NAICS | 336390: Other Motor Vehicle Parts Manufacturing |
SIC | 3714: Motor Vehicle Parts and Accessories |
Sales Range | $50 M to 100M |
# of Employees | 155 |
Plant Area |
250,000
ft2
|
Annual Production | 5,500,000
units
|
Production Hrs. Annual | 5,760
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $754,939 | 9,345,987 |
kWh
|
$0.081 |
Electricity Demand | $109,414 | 22,031 |
kW-mo/yr
|
$4.97 |
Electricity Fees | $43,109 | - |
|
- |
Natural Gas | $228,495 | 25,640 |
MMBtu
|
$8.91 |
TOTAL YEARLY COSTS | $1,135,957 | |||
RECOMMENDED SAVINGS* | $665,274 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $330,998 | $8,608,788 |
$307,928
3,810,985
kWh
|
$7,335
-
kW-mo/yr
|
$15,735 | - | |
02 | 2.3212: Optimize plant power factor | $6,141 | $6,733 | - | - | $6,141 | - | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $19,427 | $1,000 |
$16,614
205,618
kWh
|
$1,889
-
kW-mo/yr
|
$924 | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $26,555 | $8,591 |
$23,245
287,690
kWh
|
$2,048
-
kW-mo/yr
|
$1,262 | - | |
05 | 2.2437: Recover waste heat from equipment | $3,789 | $22,563 | - | - | - |
$3,789
-
MMBtu
|
|
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,369 | $17,266 |
$4,294
53,145
kWh
|
$820
-
kW-mo/yr
|
$255 | - | |
07 | 2.7135: Install occupancy sensors | $4,334 | $6,800 |
$4,128
51,094
kWh
|
- | $206 | - | |
08 | 2.7232: Replace existing hvac unit with high efficiency model | $218,857 | $1,056,464 |
$174,381
2,158,181
kWh
|
$34,074
-
kW-mo/yr
|
$10,402 | - | |
09 | 2.7243: Improve air circulation with destratification fans / other methods | $48,585 | $5,495 |
$46,276
572,726
kWh
|
- | $2,309 | - | |
10 | 2.7261: Install timers and/or thermostats | $1,219 | $79 |
$1,161
14,374
kWh
|
- | $58 | - | |
TOTAL RECOMMENDED | $665,274 | $9,733,779 |
$578,027
7,153,813
kWh
|
$46,166
-
kW-mo/yr
|
$37,292 |
$3,789
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs