Assessment Year | 2023 |
---|---|
Principal Product | Beverage |
NAICS | 311942: Spice and Extract Manufacturing |
SIC | 2082: Malt Beverages |
Sales Range | $50 M to 100M |
# of Employees | 213 |
Plant Area |
97,333
ft2
|
Annual Production | 26,500,000
units
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $693,143 | 9,748,800 |
kWh
|
$0.071 |
Electricity Demand | $268,868 | 18,441 |
kW-mo/yr
|
$14.58 |
Electricity Fees | $(-168,136.0) | - |
|
- |
Natural Gas | $347,775 | 27,914 |
MMBtu
|
$12.46 |
TOTAL YEARLY COSTS | $1,141,650 | |||
RECOMMENDED SAVINGS* | $62,975 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $30,307 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $19,205 | $8,523 |
$22,690
319,122
kWh
|
$612
-
kW-mo/yr
|
$(-4,097.0) | - | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $11,102 | $1,000 |
$12,537
176,329
kWh
|
$933
-
kW-mo/yr
|
$(-2,368.0) | - | |
03 | 2.7492: Use proper thickness of insulation on building envelope | $15,300 | $72,265 |
$18,564
261,097
kWh
|
- | $(-3,264.0) | - | |
04 | 2.7261: Install timers and/or thermostats | $8,176 | $890 |
$1,484
20,873
kWh
|
- | $(-261.0) |
$6,953
-
MMBtu
|
|
05 | 2.7232: Replace existing hvac unit with high efficiency model | $7,420 | $26,542 |
$6,466
90,946
kWh
|
$2,537
-
kW-mo/yr
|
$(-1,583.0) | - | |
06 | 2.7495: Install replacement doors | $650 | $1,640 |
$789
11,095
kWh
|
- | $(-139.0) | - | |
07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,122 | $501 |
$1,011
14,222
kWh
|
$350
-
kW-mo/yr
|
$(-239.0) | - | |
TOTAL RECOMMENDED | $62,975 | $111,361 |
$63,541
893,684
kWh
|
$4,432
-
kW-mo/yr
|
$(-11,951.0) |
$6,953
-
MMBtu
|
||
TOTAL IMPLEMENTED | $30,307 | $9,523 |
$35,227
495,451
kWh
|
$1,545
-
kW-mo/yr
|
$(-6,465.0) | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs