Assessment Year | 2022 |
---|---|
Principal Product | Steel Sheet |
NAICS | 332322: Sheet Metal Work Manufacturing |
SIC | 3444: Sheet Metal Work |
Sales Range | $5 M to 10M |
# of Employees | 50 |
Plant Area |
85,400
ft2
|
Annual Production | 12,201,411
units
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $156,646 | 5,163,200 |
kWh
|
$0.030 |
Electricity Demand | $36,586 | 5,570 |
kW-mo/yr
|
$6.57 |
Electricity Fees | $36,582 | - |
|
- |
Natural Gas | $22,718 | 1,876 |
MMBtu
|
$12.11 |
TOTAL YEARLY COSTS | $252,532 | |||
RECOMMENDED SAVINGS* | $50,682 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $21,987 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.7261: Install timers and/or thermostats | $14,348 | $2,201 |
$12,064
397,637
kWh
|
- | $2,284 | |
02 | 2.7232: Replace existing hvac unit with high efficiency model | $21,987 | $82,172 |
$14,260
470,030
kWh
|
$4,227
-
kW-mo/yr
|
$3,500 | |
03 | 2.4239: Eliminate or reduce compressed air usage | $477 | $500 |
$275
9,054
kWh
|
$126
-
kW-mo/yr
|
$76 | |
04 | 2.3212: Optimize plant power factor | $10,151 | $2,946 | - | - | $10,151 | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,719 | $7,168 |
$2,182
71,928
kWh
|
$945
-
kW-mo/yr
|
$592 | |
TOTAL RECOMMENDED | $50,682 | $94,987 |
$28,781
948,649
kWh
|
$5,298
-
kW-mo/yr
|
$16,603 | ||
TOTAL IMPLEMENTED | $21,987 | $82,172 |
$14,260
470,030
kWh
|
$4,227
-
kW-mo/yr
|
$3,500 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs