Assessment Year | 2018 |
---|---|
Principal Product | Glulam Beam |
NAICS | 321999: All Other Miscellaneous Wood Product Manufacturing |
SIC | 2499: Wood Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 40 |
Plant Area |
47,500
ft2
|
Annual Production | 10,000,000
units
|
Production Hrs. Annual | 3,146
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $117,705 | 1,177,836 |
kWh
|
$0.100 |
Electricity Demand | $30,973 | 8,230 |
kW-mo/yr
|
$3.76 |
Electricity Fees | $35,837 | - |
|
- |
Natural Gas | $43,588 | 3,490 |
MMBtu
|
$12.49 |
TOTAL YEARLY COSTS | $228,103 | |||
RECOMMENDED SAVINGS* | $30,348 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $26,914 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $13,597 | $23,433 |
$10,756
107,634
kWh
|
$2,088
-
kW-mo/yr
|
$753 | |
02 | 2.7134: Use photocell controls | $1,777 | $7,719 |
$1,661
16,624
kWh
|
- | $116 | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,238 | $2,765 |
$3,592
35,949
kWh
|
$369
-
kW-mo/yr
|
$277 | |
04 | 2.4226: Use / purchase optimum sized compressor | $3,434 | $8,870 |
$2,649
26,507
kWh
|
$560
-
kW-mo/yr
|
$225 | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,053 | $200 |
$2,528
25,294
kWh
|
$325
-
kW-mo/yr
|
$200 | |
06 | 2.3212: Optimize plant power factor | $3,682 | $2,568 | - |
$3,441
-
kW-mo/yr
|
$241 | |
07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $567 | $486 |
$435
4,350
kWh
|
$95
-
kW-mo/yr
|
$37 | |
TOTAL RECOMMENDED | $30,348 | $46,041 |
$21,621
216,358
kWh
|
$6,878
-
kW-mo/yr
|
$1,849 | ||
TOTAL IMPLEMENTED | $26,914 | $37,171 |
$18,972
189,851
kWh
|
$6,318
-
kW-mo/yr
|
$1,624 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs