Assessment Year | 2017 |
---|---|
Principal Product | Liquid Absorbants |
NAICS | 313230: Nonwoven Fabric Mills |
SIC | 2297: Non-woven Fabrics |
Sales Range | $10 M to 50M |
# of Employees | 65 |
Plant Area |
160,000
ft2
|
Annual Production | 9,000,000
lb
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $383,225 | 7,203,042 |
kWh
|
$0.053 |
Electricity Demand | $71,149 | 14,370 |
kW-mo/yr
|
$4.95 |
Electricity Fees | $51,532 | - |
|
- |
TOTAL YEARLY COSTS | $505,906 | |||
RECOMMENDED SAVINGS* | $114,078 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $62,622 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $51,456 | $17,950 |
$58,249
1,092,857
kWh
|
$8,911
-
kW-mo/yr
|
$2,940 |
$(-18,644.0)
-
MMBtu
|
- | |
02 | 2.2628: Utilize a less expensive cooling method | $42,445 | $13,900 |
$12,920
242,851
kWh
|
$2,020
-
kW-mo/yr
|
$905 | - | $26,600 | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,388 | $17,404 |
$6,879
129,300
kWh
|
$1,030
-
kW-mo/yr
|
$479 | - | - | |
04 | 2.4133: Use most efficient type of electric motors | $6,666 | $32,698 |
$5,367
100,883
kWh
|
$918
-
kW-mo/yr
|
$381 | - | - | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,257 | $390 |
$1,798
33,789
kWh
|
$330
-
kW-mo/yr
|
$129 | - | - | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,831 | $250 |
$1,483
27,881
kWh
|
$243
-
kW-mo/yr
|
$105 | - | - | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $633 | $1,165 |
$547
10,287
kWh
|
$50
-
kW-mo/yr
|
$36 | - | - | |
08 | 2.7261: Install timers and/or thermostats | $402 | $30 |
$379
7,132
kWh
|
- | $23 | - | - | |
TOTAL RECOMMENDED | $114,078 | $83,787 |
$87,622
1,644,980
kWh
|
$13,502
-
kW-mo/yr
|
$4,998 |
$(-18,644.0)
-
MMBtu
|
$26,600 | ||
TOTAL IMPLEMENTED | $62,622 | $65,837 |
$29,373
552,123
kWh
|
$4,591
-
kW-mo/yr
|
$2,058 | - | $26,600 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs