Assessment Year | 2016 |
---|---|
Principal Product | Automotive parts |
NAICS | 336320: Motor Vehicle Electrical and Electronic Equipment Manufacturing |
SIC | 3714: Motor Vehicle Parts and Accessories |
Sales Range | $100 M to 500M |
# of Employees | 400 |
Plant Area |
230,000
ft2
|
Annual Production | 800,000
units
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $655,886 | 8,918,939 |
kWh
|
$0.074 | |
Electricity Fees | $49,010 | - |
|
- | |
Natural Gas | $154,584 | 16,936 |
MMBtu
|
$9.13 | |
Waste Disposal Costs | |||||
Water Usage | $15,962 | 4,400 |
Tgal
|
$3.63 | |
TOTAL YEARLY COSTS | $875,442 | ||||
RECOMMENDED SAVINGS* | $80,762 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $15,327 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7261: Install timers and/or thermostats | $5,902 | $2,000 |
$5,592
76,044
kWh
|
$310 | - | |
02 | 2.7241: Install outside air damper / economizer on hvac unit | $17,793 | $6,200 |
$16,858
229,238
kWh
|
$935 | - | |
03 | 2.7228: Avoid introducing hot, humid, or dirty air into hvac system | $7,730 | $6,000 |
$7,324
99,587
kWh
|
$406 | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $20,058 | $79,271 |
$19,004
258,420
kWh
|
$1,054 | - | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $6,037 | $250 |
$5,720
77,782
kWh
|
$317 | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $9,425 | $4,765 |
$8,930
121,431
kWh
|
$495 | - | |
07 | 2.2437: Recover waste heat from equipment | $13,817 | $30,000 | - | - |
$13,817
-
MMBtu
|
|
TOTAL RECOMMENDED | $80,762 | $128,486 |
$63,428
862,502
kWh
|
$3,517 |
$13,817
-
MMBtu
|
||
TOTAL IMPLEMENTED | $15,327 | $6,765 |
$14,522
197,475
kWh
|
$805 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs