Assessment Year 2013
Principal Product Printed Documents
NAICS 323111: Commercial Printing (except Screen and Books)
SIC 2759: Commercial Printing, Not Elsewhere Classified
Sales Range $1
M
to 5
M
# of Employees 40
Plant Area 167,000
ft2
Annual Production 20,000,000
pieces
Production Hrs. Annual 2,470
hrs
Location (State) Alabama

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $170,395 1,744,800
kWh
Electricity Demand $27,326 5,765
kW-mo/yr
Electricity Fees $8,783 -
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $41,056 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $29,953

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $26,846 $46,099 $22,617
231,591
kWh
$3,256
-
kW-mo/yr
$973
02 2.7135: Install occupancy sensors $3,107 $5,850 $2,729
27,947
kWh
$265
-
kW-mo/yr
$113
03 2.6212: Turn off equipment during breaks, reduce operating time $7,609 $4,160 $7,333
75,086
kWh
- $276
04 2.4224: Upgrade controls on compressors $3,494 - $3,367
34,481
kWh
- $127
TOTAL RECOMMENDED $41,056 $56,109 $36,046
369,105
kWh
$3,521
-
kW-mo/yr
$1,489
TOTAL IMPLEMENTED $29,953 $51,949 $25,346
259,538
kWh
$3,521
-
kW-mo/yr
$1,086
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs