Assessment Year | 2012 |
---|---|
Principal Product | Aerospace fastners |
NAICS | 332710: Machine Shops |
SIC | 3599: Industrial and Commercial Machinery and Equipment, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 109 |
Plant Area |
58,000
ft2
|
Annual Production | 12,000,000
pieces
|
Production Hrs. Annual | 5,000
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $153,091 | 2,305,800 |
kWh
|
$0.066 |
Electricity Demand | $53,560 | 6,141 |
kW-mo/yr
|
$8.72 |
Electricity Fees | $9,698 | - |
|
- |
Natural Gas | $14,054 | 1,790 |
MMBtu
|
$7.85 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $52,931 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $7,816 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7492: Use proper thickness of insulation on building envelope | $11,862 | $26,757 |
$11,381
171,430
kWh
|
- | $481 | - | |
02 | 2.7221: Lower temperature during the winter season and vice-versa | $6,021 | $2,488 |
$5,777
87,016
kWh
|
- | $244 | - | |
03 | 2.7442: Keep doors and windows shut when not on use | $5,678 | $142 |
$5,448
82,060
kWh
|
- | $230 | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $10,518 | $13,900 |
$6,805
102,504
kWh
|
$3,286
-
kW-mo/yr
|
$427 | - | |
05 | 2.2437: Recover waste heat from equipment | $6,230 | $4,203 | - | - | $240 |
$5,990
-
MMBtu
|
|
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,138 | $2,200 |
$1,545
23,267
kWh
|
$507
-
kW-mo/yr
|
$86 | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,484 | $12,249 |
$7,648
115,200
kWh
|
$2,411
-
kW-mo/yr
|
$425 | - | |
TOTAL RECOMMENDED | $52,931 | $61,939 |
$38,604
581,477
kWh
|
$6,204
-
kW-mo/yr
|
$2,133 |
$5,990
-
MMBtu
|
||
TOTAL IMPLEMENTED | $7,816 | $2,342 |
$6,993
105,327
kWh
|
$507
-
kW-mo/yr
|
$316 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs