Assessment Year | 2011 |
---|---|
Principal Product | Plastic Medical Supplies |
NAICS | 339112: Surgical and Medical Instrument Manufacturing |
SIC | 3841: Surgical and Medical Instruments and Apparatus |
Sales Range | $5 M to 10M |
# of Employees | 173 |
Plant Area |
115,000
ft2
|
Annual Production | 9,999,999,999
units
|
Production Hrs. Annual | 3,094
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $296,299 | 4,883,380 |
kWh
|
$0.061 |
Electricity Demand | $109,035 | 9,755 |
kW-mo/yr
|
$11.18 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $58,724 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $44,289 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.7261: Install timers and/or thermostats | $16,400 | $5,100 |
$15,020
165,729
kWh
|
- | $1,380 | |
02 | 2.4235: Remove or close off unneeded compressed air lines | $15,438 | $13,988 |
$14,138
241,822
kWh
|
- | $1,300 | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $10,210 | $4,238 |
$7,420
126,949
kWh
|
$1,930
-
kW-mo/yr
|
$860 | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,451 | $46,341 |
$7,325
125,319
kWh
|
$4,077
-
kW-mo/yr
|
$1,049 | |
05 | 2.7122: Disconnect ballasts | $3,015 | $607 |
$929
15,900
kWh
|
$1,832
-
kW-mo/yr
|
$254 | |
06 | 2.7135: Install occupancy sensors | $1,210 | $2,719 |
$1,108
18,954
kWh
|
- | $102 | |
TOTAL RECOMMENDED | $58,724 | $72,993 |
$45,940
694,673
kWh
|
$7,839
-
kW-mo/yr
|
$4,945 | ||
TOTAL IMPLEMENTED | $44,289 | $65,429 |
$36,483
532,870
kWh
|
$4,077
-
kW-mo/yr
|
$3,729 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs