Assessment Year | 2011 |
---|---|
Principal Product | Plastic containers |
NAICS | 326160: Plastics Bottle Manufacturing |
SIC | 3085: Plastics Bottles |
Sales Range | $5 M to 10M |
# of Employees | 62 |
Plant Area |
45,600
ft2
|
Annual Production | 1
units
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $281,351 | 4,230,649 |
kWh
|
$0.067 |
Electricity Demand | $69,550 | 11,918 |
kW-mo/yr
|
$5.84 |
Electricity Fees | $286 | - |
|
- |
Natural Gas | $3,738 | 257 |
MMBtu
|
$14.54 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $78,860 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $68,415 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $3,454 | $10,130 |
$3,169
47,626
kWh
|
$35
-
kW-mo/yr
|
$250 | - | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $5,593 | $800 |
$5,593
84,056
kWh
|
- | - | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,323 | $2,200 |
$2,323
34,915
kWh
|
- | - | - | |
04 | 2.7261: Install timers and/or thermostats | $1,325 | $340 |
$71
1,058
kWh
|
- | - |
$1,254
-
MMBtu
|
|
05 | 2.7314: Reduce ventilation air | $6,532 | $4,798 |
$6,060
91,066
kWh
|
- | $472 | - | |
06 | 2.7232: Replace existing hvac unit with high efficiency model | $45,899 | $74,275 |
$42,578
639,885
kWh
|
- | $3,321 | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,336 | $19,786 |
$9,925
149,160
kWh
|
$1,518
-
kW-mo/yr
|
$893 | - | |
08 | 2.7135: Install occupancy sensors | $1,398 | $448 |
$1,297
19,486
kWh
|
- | $101 | - | |
TOTAL RECOMMENDED | $78,860 | $112,777 |
$71,016
1,067,252
kWh
|
$1,553
-
kW-mo/yr
|
$5,037 |
$1,254
-
MMBtu
|
||
TOTAL IMPLEMENTED | $68,415 | $101,399 |
$60,957
916,084
kWh
|
$1,518
-
kW-mo/yr
|
$4,686 |
$1,254
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs