Assessment Year | 2023 |
---|---|
Principal Product | Plastic Closures |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $100 M to 500M |
# of Employees | 110 |
Plant Area |
265,450
ft2
|
Annual Production | 26,212,175
lb
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Tennessee |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $1,148,826 | 17,334,230 |
kWh
|
$0.066 | |
Electricity Demand | $437,429 | 29,472 |
kW-mo/yr
|
$14.84 | |
Electricity Fees | $29,657 | - |
|
- | |
Natural Gas | $53,305 | 4,002 |
MMBtu
|
$13.32 | |
Waste Disposal Costs | |||||
Water Usage | $33,070 | 8,404 |
Tgal
|
$3.94 | |
Water Disposal | $91,798 | 8,404 |
Tgal
|
$10.92 | |
TOTAL YEARLY COSTS | $1,794,085 | ||||
RECOMMENDED SAVINGS* | $82,684 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 3.4116: Meter recycled water (to reduce sewer charges) | $23,724 | $60 | - | - | - | $23,724 | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $15,633 | $1,785 |
$15,633
235,789
kWh
|
- | - | - | |
03 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $10,858 | $7,500 |
$8,231
124,158
kWh
|
$2,627
-
kW-mo/yr
|
- | - | |
04 | 2.6212: Turn off equipment during breaks, reduce operating time | $8,231 | $3,100 |
$3,244
48,929
kWh
|
$4,987
-
kW-mo/yr
|
- | - | |
05 | 2.7241: Install outside air damper / economizer on hvac unit | $5,905 | $1,050 |
$5,905
89,072
kWh
|
- | - | - | |
06 | 2.9114: Use solar heat to make electricty | $5,202 | $21,100 |
$5,202
78,813
kWh
|
- | - | - | |
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,887 | $113 |
$3,887
58,632
kWh
|
- | - | - | |
08 | 2.2621: Modify refrigeration system to operate at a lower pressure | $2,558 | $3,750 |
$1,935
29,192
kWh
|
$623
-
kW-mo/yr
|
- | - | |
09 | 2.4221: Install compressor air intakes in coolest locations | $2,170 | $7,500 |
$2,170
32,732
kWh
|
- | - | - | |
10 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,966 | $6,750 |
$1,966
29,652
kWh
|
- | - | - | |
11 | 2.7224: Reduce space conditioning during non-working hours | $1,643 | $100 |
$1,643
24,780
kWh
|
- | - | - | |
12 | 2.7231: Use radiant heater for spot heating | $907 | $2,724 | - | - |
$907
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $82,684 | $55,532 |
$49,816
751,749
kWh
|
$8,237
-
kW-mo/yr
|
$907
-
MMBtu
|
$23,724 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs