Assessment Year | 2016 |
---|---|
Principal Product | Exhaust Components |
NAICS | 336390: Other Motor Vehicle Parts Manufacturing |
SIC | 3714: Motor Vehicle Parts and Accessories |
Sales Range | $10 M to 50M |
# of Employees | 241 |
Plant Area |
87,000
ft2
|
Annual Production | 975,000
pieces
|
Production Hrs. Annual | 4,550
hrs
|
Location (State) | Tennessee |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $161,054 | 2,525,760 |
kWh
|
$0.064 |
Electricity Demand | $132,388 | 9,773 |
kW-mo/yr
|
$13.55 |
Natural Gas | $32,051 | 3,113 |
MMBtu
|
$10.30 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $107,116 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $48,954 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.6212: Turn off equipment during breaks, reduce operating time | $30,026 | $4,452 |
$30,026
469,107
kWh
|
- | - | - | |
02 | 2.3212: Optimize plant power factor | $27,708 | $28,000 | - |
$27,708
-
kW-mo/yr
|
- | - | |
03 | 2.8114: Change rate schedules or other changes in utility service | $20,627 | $5,200 | - | - | - | $20,627 | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,188 | $170,642 |
$9,259
144,678
kWh
|
$2,929
-
kW-mo/yr
|
- | - | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $5,407 | $125 |
$3,470
54,219
kWh
|
$1,937
-
kW-mo/yr
|
- | - | |
06 | 2.1135: Repair furnaces and oven doors so that they seal efficiently | $5,213 | $900 |
$5,213
81,464
kWh
|
- | - | - | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,887 | $3,000 |
$1,627
25,419
kWh
|
$260
-
kW-mo/yr
|
- | - | |
08 | 2.2437: Recover waste heat from equipment | $1,764 | $500 | - | - |
$1,764
-
MMBtu
|
- | |
09 | 2.7261: Install timers and/or thermostats | $1,481 | $500 |
$904
14,120
kWh
|
- |
$577
-
MMBtu
|
- | |
10 | 2.6212: Turn off equipment during breaks, reduce operating time | $815 | $2,500 |
$815
12,740
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $107,116 | $215,819 |
$51,314
801,747
kWh
|
$32,834
-
kW-mo/yr
|
$2,341
-
MMBtu
|
$20,627 | ||
TOTAL IMPLEMENTED | $48,954 | $202,267 |
$14,356
224,316
kWh
|
$32,834
-
kW-mo/yr
|
$1,764
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs