| Assessment Year | 2015 |
|---|---|
| Principal Product | metal can ends |
| NAICS | 332431: Metal Can Manufacturing |
| SIC | 3411: Metal Cans |
| Sales Range | $100 M to 500M |
| # of Employees | 206 |
| Plant Area |
210,652
ft2
|
| Annual Production | 204,300,401,502
pieces
|
| Production Hrs. Annual | 8,400
hrs
|
| Location (State) | Tennessee |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $900,909 | 14,475,618 |
kWh
|
$0.062 |
| Electricity Demand | $290,742 | 26,321 |
kW-mo/yr
|
$11.05 |
| Natural Gas | $325,538 | 52,993 |
MMBtu
|
$6.14 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $292,600 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $205,506 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $51,147 | $344,210 |
$41,014
661,531
kWh
|
$1,037
-
kW-mo/yr
|
- | $9,096 | |
| 02 | 2.3132: Recharge batteries on during off-peak demand periods | $39,567 | - | - |
$39,567
-
kW-mo/yr
|
- | - | |
| 03 | 2.4224: Upgrade controls on compressors | $32,298 | $15,201 |
$25,745
415,246
kWh
|
$6,553
-
kW-mo/yr
|
- | - | |
| 04 | 2.2515: Use optimum thickness insulation | $32,011 | $40,000 | - | - |
$32,011
-
MMBtu
|
- | |
| 05 | 2.4224: Upgrade controls on compressors | $26,007 | $26,000 |
$25,466
410,745
kWh
|
$541
-
kW-mo/yr
|
- | - | |
| 06 | 2.7243: Improve air circulation with destratification fans / other methods | $29,361 | $9,500 |
$16,739
269,992
kWh
|
- |
$12,622
-
MMBtu
|
- | |
| 07 | 2.4239: Eliminate or reduce compressed air usage | $25,293 | $3,465 |
$24,943
402,269
kWh
|
$350
-
kW-mo/yr
|
- | - | |
| 08 | 2.7425: Clean or color roof to reduce solar load | $26,456 | $157,989 |
$27,144
437,821
kWh
|
$4,423
-
kW-mo/yr
|
$(-5,111.0)
-
MMBtu
|
- | |
| 09 | 2.4224: Upgrade controls on compressors | $26,246 | $2,400 |
$26,246
423,297
kWh
|
- | - | - | |
| 10 | 2.1113: Reduce combustion air flow to optimum | $2,978 | $1,000 | - | - |
$2,978
-
MMBtu
|
- | |
| 11 | 2.4133: Use most efficient type of electric motors | $958 | $2,131 |
$693
11,178
kWh
|
$265
-
kW-mo/yr
|
- | - | |
| 12 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $278 | $240 |
$133
2,145
kWh
|
$33
-
kW-mo/yr
|
- | $112 | |
| TOTAL RECOMMENDED | $292,600 | $602,136 |
$188,123
3,034,224
kWh
|
$52,769
-
kW-mo/yr
|
$42,500
-
MMBtu
|
$9,208 | ||
| TOTAL IMPLEMENTED | $205,506 | $214,795 |
$146,416
2,361,515
kWh
|
$51,467
-
kW-mo/yr
|
$7,511
-
MMBtu
|
$112 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs