Assessment Year | 2009 |
---|---|
Principal Product | Vacuum Cleaning Equipment |
NAICS | 335210: Small Electrical Appliance Manufacturing |
SIC | 3635: Household Vacuum Cleaners |
Sales Range | less than $500 k |
# of Employees | 370 |
Plant Area |
310,000
ft2
|
Annual Production | 8,000,000
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Tennessee |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $723,421 | 12,178,800 |
kWh
|
$0.059 |
Electricity Demand | $91,793 | 21,557 |
kW-mo/yr
|
$4.26 |
Electricity Fees | $12,228 | - |
|
- |
Natural Gas | $96,133 | 7,214 |
MMBtu
|
$13.33 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $55,600 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $9,300 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.4226: Use / purchase optimum sized compressor | $20,000 | $47,500 |
$15,780
228,689
kWh
|
$4,220
-
kW-mo/yr
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,800 | $2,500 |
$4,800
69,293
kWh
|
- | - | |
03 | 2.4322: Use or replace with energy efficient substitutes | $3,250 | $4,800 | - | - | $3,250 | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,900 | $800 |
$2,900
32,675
kWh
|
- | - | |
05 | 2.2628: Utilize a less expensive cooling method | $13,300 | $20,000 |
$13,300
224,000
kWh
|
- | - | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,950 | $5,000 |
$3,700
62,160
kWh
|
$1,250
-
kW-mo/yr
|
- | |
07 | 2.2623: Minimize condenser cooling water temperature | $4,000 | - |
$3,000
50,400
kWh
|
$1,000
-
kW-mo/yr
|
- | |
08 | 2.2625: Chill water to the highest temperature possible | $2,400 | - |
$1,800
30,240
kWh
|
$600
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $55,600 | $80,600 |
$45,280
697,457
kWh
|
$7,070
-
kW-mo/yr
|
$3,250 | ||
TOTAL IMPLEMENTED | $9,300 | $800 |
$7,700
113,315
kWh
|
$1,600
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs