| Assessment Year | 2008 |
|---|---|
| Principal Product | Electrical Outlet Boxes |
| NAICS | 335931: Current-Carrying Wiring Device Manufacturing |
| SIC | 3644: Noncurrent-Carrying Wiring Devices |
| Sales Range | $100 M to 500M |
| # of Employees | 379 |
| Plant Area |
3,250,000
ft2
|
| Annual Production | 48,780
ton
|
| Production Hrs. Annual | 6,500
hrs
|
| Location (State) | Tennessee |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $675,270 | 16,645,080 |
kWh
|
$0.041 |
| Electricity Demand | $538,444 | 34,362 |
kW-mo/yr
|
$15.67 |
| Electricity Fees | $30,107 | - |
|
- |
| Natural Gas | $208,705 | 16,667 |
MMBtu
|
$12.52 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $276,120 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.1113: Reduce combustion air flow to optimum | $10,000 | $2,500 | - | - |
$10,000
-
MMBtu
|
- | |
| 02 | 2.2136: Install / repair insulation on steam lines | $23,950 | $15,491 | - | - |
$23,950
-
MMBtu
|
- | |
| 03 | 2.4224: Upgrade controls on compressors | $23,300 | $50,530 |
$23,300
466,772
kWh
|
- | - | - | |
| 04 | 2.2113: Repair or replace steam traps | $7,750 | $4,800 |
$7,750
161,500
kWh
|
- | - | - | |
| 05 | 2.4239: Eliminate or reduce compressed air usage | $13,400 | $13,400 |
$13,400
278,800
kWh
|
- | - | - | |
| 06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $22,600 | $10,900 |
$22,600
470,900
kWh
|
- | - | - | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $154,961 | $376,774 |
$86,870
1,810,166
kWh
|
$47,591
-
kW-mo/yr
|
- | $20,500 | |
| 08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,022 | $14,263 |
$4,638
96,654
kWh
|
$3,710
-
kW-mo/yr
|
- | $1,674 | |
| 09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,966 | $13,554 |
$2,388
49,751
kWh
|
$3,525
-
kW-mo/yr
|
- | $1,053 | |
| 10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,304 | $26,136 |
$633
13,200
kWh
|
$507
-
kW-mo/yr
|
- | $1,164 | |
| 11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $308 | $150 |
$76
1,584
kWh
|
$61
-
kW-mo/yr
|
- | $171 | |
| 12 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $559 | $683 |
$212
4,415
kWh
|
$116
-
kW-mo/yr
|
- | $231 | |
| TOTAL RECOMMENDED | $276,120 | $529,181 |
$161,867
3,353,742
kWh
|
$55,510
-
kW-mo/yr
|
$33,950
-
MMBtu
|
$24,793 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs