| Assessment Year | 2007 |
|---|---|
| Principal Product | Shirts and Jeans |
| NAICS | 313310: Textile and Fabric Finishing Mills |
| SIC | 2269: Finishers of Textiles, Not elsewhere Classified |
| Sales Range | $500 k to 1M |
| # of Employees | 70 |
| Plant Area |
44,000
ft2
|
| Annual Production | 100,000
pieces
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Tennessee |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $48,579 | 813,000 |
kWh
|
$0.060 |
| Electricity Demand | $31,535 | 3,026 |
kW-mo/yr
|
$10.42 |
| Electricity Fees | $7,734 | - |
|
- |
| Natural Gas | $83,949 | 7,321 |
MMBtu
|
$11.47 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $80,059 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.3212: Optimize plant power factor | $9,260 | $30,000 | - | $9,260 | - | |
| 02 | 2.1224: Replace boiler | $1,896 | $15,000 | - | - |
$1,896
-
MMBtu
|
|
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $38,338 | $42,670 |
$38,338
357,988
kWh
|
- | - | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,406 | $5,360 |
$1,406
10,847
kWh
|
- | - | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $250 | $450 |
$250
2,831
kWh
|
- | - | |
| 06 | 2.2437: Recover waste heat from equipment | $3,379 | $1,500 | - | - |
$3,379
-
MMBtu
|
|
| 07 | 2.2511: Insulate bare equipment | $5,016 | $1,000 | - | - |
$5,016
-
MMBtu
|
|
| 08 | 2.4227: Use compressor air filters | $1,524 | $400 |
$1,524
19,242
kWh
|
- | - | |
| 09 | 2.4239: Eliminate or reduce compressed air usage | $2,592 | $2,250 |
$2,592
25,920
kWh
|
- | - | |
| 10 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $11,574 | $1,100 |
$11,574
115,740
kWh
|
- | - | |
| 11 | 2.8121: Apply for tax-free status for energy purchases | $4,824 | - | - | $4,824 | - | |
| TOTAL RECOMMENDED | $80,059 | $99,730 |
$55,684
532,568
kWh
|
$14,084 |
$10,291
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Fees Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs