Assessment Year | 2024 |
---|---|
Principal Product | Lemons, Limes, Mandarins, Navel Oranges, Balencias Oranges, Mineola |
NAICS | 311411: Frozen Fruit, Juice, and Vegetable Manufacturing |
SIC | 2037: Frozen Fruits, Fruit Juices, and Vegetables |
Sales Range | $10 M to 50M |
# of Employees | 315 |
Plant Area |
6,808,312
ft2
|
Annual Production | 4,000,000
units
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $250,681 | 7,334,650 |
kWh
|
$0.034 |
Electricity Demand | $205,376 | 16,708 |
kW-mo/yr
|
$12.29 |
Electricity Fees | $27,609 | - |
|
- |
Natural Gas | $224,195 | 82,728 |
MMBtu
|
$2.71 |
LPG | $108,764 | 43,505 |
MMBtu
|
$2.50 |
TOTAL YEARLY COSTS | $816,625 | |||
RECOMMENDED SAVINGS* | $201,871 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $33,304 | $43,319 |
$31,815
1,060,486
kWh
|
$1,489
-
kW-mo/yr
|
- | |
02 | 2.7135: Install occupancy sensors | $14,601 | $10,663 |
$14,432
481,082
kWh
|
$169
-
kW-mo/yr
|
- | |
03 | 2.8121: Apply for tax-free status for energy purchases | $27,609 | $2,500 | - | - | $27,609 | |
04 | 2.2523: Reduce infiltration to refrigerated areas; isolate hot equipment from refrigerated areas | $3,211 | $8,620 |
$2,056
68,536
kWh
|
$1,155
-
kW-mo/yr
|
- | |
05 | 2.9114: Use solar heat to make electricty | $116,063 | $1,521,071 |
$66,772
2,127,865
kWh
|
$49,290
-
kW-mo/yr
|
- | |
06 | 2.4224: Upgrade controls on compressors | $6,430 | $15,000 |
$4,118
137,250
kWh
|
$2,313
-
kW-mo/yr
|
- | |
07 | 2.4221: Install compressor air intakes in coolest locations | $654 | $1,350 |
$419
13,957
kWh
|
$235
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $201,871 | $1,602,523 |
$119,612
3,889,176
kWh
|
$54,650
-
kW-mo/yr
|
$27,609 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs