| Assessment Year | 2017 |
|---|---|
| Principal Product | Windshield Wiper Components |
| NAICS | 336390: Other Motor Vehicle Parts Manufacturing |
| SIC | 3714: Motor Vehicle Parts and Accessories |
| Sales Range | $50 M to 100M |
| # of Employees | 230 |
| Plant Area |
370,000
ft2
|
| Annual Production | 50,000,000
pieces
|
| Production Hrs. Annual | 8,544
hrs
|
| Location (State) | Texas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $1,185,706 | 22,500,000 |
kWh
|
$0.053 | |
| Electricity Demand | $333,041 | 42,604 |
kW-mo/yr
|
$7.82 | |
| Electricity Fees | $32,707 | - |
|
- | |
| Natural Gas | $63,977 | 7,428 |
MMBtu
|
$8.61 | |
| Waste Disposal Costs | |||||
| Water Usage | $54,220 | 20,010,000 |
Tgal
|
$0.003 | |
| Water Disposal | $76,884 | 20,010 |
Tgal
|
$3.84 | |
| TOTAL YEARLY COSTS | $1,746,535 | ||||
| RECOMMENDED SAVINGS* | $223,526 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $30,038 | $21,816 |
$30,038
447,188
kWh
|
- | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $271 | $279 |
$271
4,039
kWh
|
- | - | |
| 03 | 2.2511: Insulate bare equipment | $5,324 | $88 |
$2,208
32,876
kWh
|
- |
$3,116
-
MMBtu
|
|
| 04 | 2.2523: Reduce infiltration to refrigerated areas; isolate hot equipment from refrigerated areas | $31,644 | - |
$31,644
471,101
kWh
|
- | - | |
| 05 | 2.2531: Re-size charging openings or add movable cover or door | $4,005 | $208 |
$4,005
59,623
kWh
|
- | - | |
| 06 | 2.7447: Install vinyl strip / high speed / air curtain doors | $117,470 | $11,908 |
$117,470
1,748,846
kWh
|
- | - | |
| 07 | 2.7243: Improve air circulation with destratification fans / other methods | $11,119 | $3,360 |
$11,119
165,533
kWh
|
- | - | |
| 08 | 2.3132: Recharge batteries on during off-peak demand periods | $23,655 | - | - |
$23,655
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $223,526 | $37,659 |
$196,755
2,929,206
kWh
|
$23,655
-
kW-mo/yr
|
$3,116
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs