Assessment Year | 1992 |
---|---|
Principal Product | MOP YARN AND MOP HEADS |
NAICS |
n/a
|
SIC | 2392: House furnishing, Except Curtains and Draperies |
Sales Range | $10 M to 50M |
# of Employees | 225 |
Plant Area |
n/a
|
Annual Production | 6,000,000
pieces
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Tennessee |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $368,961 | 6,145,369 |
kWh
|
$0.060 |
Natural Gas | $19,807 | 3,753 |
MMBtu
|
$5.28 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $118,475 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.7123: Keep lamps and reflectors clean | $41,641 | $47,895 |
$38,986
649,766
kWh
|
- | $2,655 | |
02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $2,756 | $1,000 | - |
$2,756
-
MMBtu
|
- | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $9,074 | $1,380 |
$9,074
151,231
kWh
|
- | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $17,188 | $2,188 |
$15,000
250,000
kWh
|
- | $2,188 | |
05 | 2.6211: Conserve energy by efficient use of vending machines | $1,758 | $1,535 |
$1,758
29,308
kWh
|
- | - | |
06 | 2.7221: Lower temperature during the winter season and vice-versa | $1,178 | - |
$1,178
19,637
kWh
|
- | - | |
07 | 2.4221: Install compressor air intakes in coolest locations | $598 | $480 |
$598
9,965
kWh
|
- | - | |
08 | 2.3212: Optimize plant power factor | $29,700 | $32,400 |
$29,700
-
kWh
|
- | - | |
09 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $14,582 | - |
$14,582
-
kWh
|
- | - | |
TOTAL RECOMMENDED | $118,475 | $86,878 |
$110,876
1,109,907
kWh
|
$2,756
-
MMBtu
|
$4,843 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs