| Assessment Year | 1992 |
|---|---|
| Principal Product | FLASHERS,CIRCUIT BREAKER |
| NAICS |
n/a
|
| SIC | 3647: Vehicular Lighting Equipment |
| Sales Range | $10 M to 50M |
| # of Employees | 250 |
| Plant Area |
n/a
|
| Annual Production | 27,375,000
pieces
|
| Production Hrs. Annual | 6,000
hrs
|
| Location (State) | Tennessee |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $325,296 | 5,834,994 |
kWh
|
$0.056 |
| Natural Gas | $18,889 | 3,105 |
MMBtu
|
$6.08 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $19,012 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $19,012 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4221: Install compressor air intakes in coolest locations | $1,646 | $860 |
$1,646
29,601
kWh
|
- | |
| 02 | 2.4312: Improve lubrication practices | $788 | $300 |
$788
14,068
kWh
|
- | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $414 | $316 |
$1,446
26,084
kWh
|
$(-1,032.0) | |
| 04 | 2.6212: Turn off equipment during breaks, reduce operating time | $706 | $890 |
$706
12,603
kWh
|
- | |
| 05 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $11,058 | - |
$11,058
-
kWh
|
- | |
| 06 | 2.3212: Optimize plant power factor | $4,400 | $9,000 |
$4,400
-
kWh
|
- | |
| TOTAL RECOMMENDED | $19,012 | $11,366 |
$20,044
82,356
kWh
|
$(-1,032.0) | ||
| TOTAL IMPLEMENTED | $19,012 | $11,366 |
$20,044
82,356
kWh
|
$(-1,032.0) | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs