Assessment Year | 1988 |
---|---|
Principal Product | TEXTILE DYEING |
NAICS |
n/a
|
SIC | 2269: Finishers of Textiles, Not elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 180 |
Plant Area |
n/a
|
Annual Production | 144,000
thousand feet
|
Production Hrs. Annual | 6,336
hrs
|
Location (State) | Tennessee |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $290,000 | 5,400,645 |
kWh
|
$0.054 |
Natural Gas | $765,976 | 184,710 |
MMBtu
|
$4.15 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $127,696 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $67,352 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.2135: Repair and eliminate steam leaks | $33,546 | $10,370 | - |
$33,546
-
MMBtu
|
|
02 | 2.2163: Use minimum steam operating pressure | $29,352 | $31,700 | - |
$29,352
-
MMBtu
|
|
03 | 2.2511: Insulate bare equipment | $14,539 | $3,576 | - |
$14,539
-
MMBtu
|
|
04 | 2.2449: Recover heat from exhausted steam, hot air or hot water | $10,849 | $43,400 | - |
$10,849
-
MMBtu
|
|
05 | 2.1233: Analyze flue gas for proper air/fuel ratio | $8,180 | $600 | - |
$8,180
-
MMBtu
|
|
06 | 2.7243: Improve air circulation with destratification fans / other methods | $7,585 | $10,200 | - |
$7,585
-
MMBtu
|
|
07 | 2.2136: Install / repair insulation on steam lines | $2,687 | $1,379 | - |
$2,687
-
MMBtu
|
|
08 | 2.7141: Lower light fixtures in high ceiling areas | $5,476 | $13,845 |
$5,476
101,407
kWh
|
- | |
09 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $7,706 | - |
$7,706
142,732
kWh
|
- | |
10 | 2.2511: Insulate bare equipment | $1,857 | $2,148 | - |
$1,857
-
MMBtu
|
|
11 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,909 | $240 |
$3,909
72,392
kWh
|
- | |
12 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,187 | $645 |
$1,187
21,981
kWh
|
- | |
13 | 2.4312: Improve lubrication practices | $475 | $150 |
$475
8,792
kWh
|
- | |
14 | 2.4221: Install compressor air intakes in coolest locations | $348 | $615 |
$348
6,448
kWh
|
- | |
TOTAL RECOMMENDED | $127,696 | $118,868 |
$19,101
353,752
kWh
|
$108,595
-
MMBtu
|
||
TOTAL IMPLEMENTED | $67,352 | $56,139 |
$12,090
223,916
kWh
|
$55,262
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs