| Assessment Year | 2005 |
|---|---|
| Principal Product | Industrial Valves |
| NAICS | 332911: Industrial Valve Manufacturing |
| SIC | 3494: Valves and Pipe Fittings, Not Elsewhere Classified |
| Sales Range | $100 M to 500M |
| # of Employees | 480 |
| Plant Area |
255,475
ft2
|
| Annual Production | 6,696,936
thousand feet
|
| Production Hrs. Annual | 6,032
hrs
|
| Location (State) | Texas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $731,685 | 13,954,914 |
kWh
|
$0.052 |
| Electricity Demand | $206,020 | 35,368 |
kW-mo/yr
|
$5.83 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $179,676 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $25,860 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7447: Install vinyl strip / high speed / air curtain doors | $136,425 | $38,485 |
$136,425
2,667,410
kWh
|
- | |
| 02 | 2.2511: Insulate bare equipment | $15,690 | $1,015 |
$15,690
306,750
kWh
|
- | |
| 03 | 2.7447: Install vinyl strip / high speed / air curtain doors | $14,111 | $7,705 |
$14,111
275,908
kWh
|
- | |
| 04 | 2.7447: Install vinyl strip / high speed / air curtain doors | $3,280 | $1,485 |
$3,280
64,156
kWh
|
- | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,925 | $205 |
$3,245
63,448
kWh
|
$680
-
kW-mo/yr
|
|
| 06 | 2.2511: Insulate bare equipment | $2,400 | $995 |
$2,400
47,070
kWh
|
- | |
| 07 | 2.2511: Insulate bare equipment | $1,530 | $570 |
$1,530
29,985
kWh
|
- | |
| 08 | 2.4238: Do not use compressed air for personal cooling | $850 | - |
$460
9,000
kWh
|
$390
-
kW-mo/yr
|
|
| 09 | 2.7135: Install occupancy sensors | $965 | $200 |
$965
18,877
kWh
|
- | |
| 10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $500 | - |
$415
8,100
kWh
|
$85
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $179,676 | $50,660 |
$178,521
3,490,704
kWh
|
$1,155
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | $25,860 | $2,985 |
$24,705
483,230
kWh
|
$1,155
-
kW-mo/yr
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs