Assessment Year | 2005 |
---|---|
Principal Product | Turbo Compressors |
NAICS | 333911: Pump and Pumping Equipment Manufacturing |
SIC | 3561: Pumps and Pumping Equipment |
Sales Range | $10 M to 50M |
# of Employees | 75 |
Plant Area |
60,000
ft2
|
Annual Production | 11,000
pieces
|
Production Hrs. Annual | 5,572
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $214,188 | 3,894,396 |
kWh
|
$0.055 |
Electricity Demand | $58,230 | 11,853 |
kW-mo/yr
|
$4.91 |
Natural Gas | $22,407 | 3,142 |
MMBtu
|
$7.13 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $28,975 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $16,710 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (non-haz) Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4226: Use / purchase optimum sized compressor | $9,280 | $2,300 |
$6,880
115,470
kWh
|
$2,400
-
kW-mo/yr
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $9,280 | $1,300 |
$7,820
131,300
kWh
|
$1,460
-
kW-mo/yr
|
- | - | |
03 | 2.7229: Air condition only space necessary | $3,580 | $5 | - | - |
$3,580
-
MMBtu
|
- | |
04 | 3.7214: Reduce or eliminate waste | $2,710 | $36 | - | - | - |
$2,710
-
gal
|
|
05 | 2.7311: Ventilation system to shut off when room is not in use | $2,200 | $111 |
$2,200
37,400
kWh
|
- | - | - | |
06 | 2.6215: Shut off air conditioning in winter heating season | $1,140 | - |
$1,140
19,183
kWh
|
- | - | - | |
07 | 2.7132: Install timers on light switches in little used areas | $535 | $155 |
$535
8,973
kWh
|
- | - | - | |
08 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $250 | - |
$165
2,757
kWh
|
$85
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $28,975 | $3,907 |
$18,740
315,083
kWh
|
$3,945
-
kW-mo/yr
|
$3,580
-
MMBtu
|
$2,710
-
gal
|
||
TOTAL IMPLEMENTED | $16,710 | $1,341 |
$8,960
150,483
kWh
|
$1,460
-
kW-mo/yr
|
$3,580
-
MMBtu
|
$2,710
-
gal
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs