Assessment Year | 2004 |
---|---|
Principal Product | Electronic Connectors |
NAICS | 334417: Electronic Connector Manufacturing |
SIC | 3678: Electronic Connectors |
Sales Range | $10 M to 50M |
# of Employees | 186 |
Plant Area |
32,600
ft2
|
Annual Production | 51,000,000
pieces
|
Production Hrs. Annual | 5,560
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $235,959 | 4,574,626 |
kWh
|
$0.052 |
Electricity Demand | $84,902 | 18,365 |
kW-mo/yr
|
$4.62 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $76,523 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $16,391 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Water Disposal Savings | Other Liquid (non-haz) Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $36,101 | $25,800 |
$36,101
500,500
kWh
|
- | - | - | - | - | |
02 | 2.4239: Eliminate or reduce compressed air usage | $21,003 | $12,967 |
$17,758
245,581
kWh
|
$3,245
-
kW-mo/yr
|
- | - | - | - | |
03 | 2.8121: Apply for tax-free status for energy purchases | $10,113 | - | - | - | $10,113 | - | - | - | |
04 | 2.6218: Turn off equipment when not in use | $3,277 | - |
$3,277
63,274
kWh
|
- | - | - | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,001 | $720 |
$2,603
36,086
kWh
|
$398
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.6231: Utilize controls to operate equipment only when needed | $1,680 | $732 |
$1,473
20,419
kWh
|
$207
-
kW-mo/yr
|
- | - | - | - | |
07 | 3.5313: Increase amount of waste recovered for resale | $880 | - | - | - | - |
$550
-
Tgal
|
- | $330 | |
08 | 3.5316: Contract a wood pallet recycling company | $468 | - | - | - | - | - |
$468
-
gal
|
- | |
TOTAL RECOMMENDED | $76,523 | $40,219 |
$61,212
865,860
kWh
|
$3,850
-
kW-mo/yr
|
$10,113 |
$550
-
Tgal
|
$468
-
gal
|
$330 | ||
TOTAL IMPLEMENTED | $16,391 | $720 |
$5,880
99,360
kWh
|
$398
-
kW-mo/yr
|
$10,113 | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Water Disposal Savings | Other Liquid (non-haz) Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs