Assessment Year | 2004 |
---|---|
Principal Product | Direct Mai Printing & Marketing |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2759: Commercial Printing, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 180 |
Plant Area |
69,000
ft2
|
Annual Production | 80,000,000
pieces
|
Production Hrs. Annual | 8,568
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $83,279 | 1,626,975 |
kWh
|
$0.051 |
Electricity Demand | $30,007 | 3,977 |
kW-mo/yr
|
$7.55 |
Electricity Fees | $9,514 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $29,302 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $27,272 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.8114: Change rate schedules or other changes in utility service | $9,482 | - | - | - | $9,482 | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,293 | $9,519 |
$5,853
116,926
kWh
|
$2,440
-
kW-mo/yr
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,975 | $10,974 |
$4,300
85,983
kWh
|
$3,675
-
kW-mo/yr
|
- | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $800 | $316 |
$359
7,173
kWh
|
$441
-
kW-mo/yr
|
- | |
05 | 2.4226: Use / purchase optimum sized compressor | $1,120 | $2,130 | - |
$1,120
-
kW-mo/yr
|
- | |
06 | 2.4224: Upgrade controls on compressors | $910 | $190 |
$910
18,216
kWh
|
- | - | |
07 | 2.7135: Install occupancy sensors | $371 | $284 |
$371
7,405
kWh
|
- | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $351 | $542 |
$270
5,380
kWh
|
$81
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $29,302 | $23,955 |
$12,063
241,083
kWh
|
$7,757
-
kW-mo/yr
|
$9,482 | ||
TOTAL IMPLEMENTED | $27,272 | $21,635 |
$11,153
222,867
kWh
|
$6,637
-
kW-mo/yr
|
$9,482 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs