Assessment Year | 2003 |
---|---|
Principal Product | Partitions and Fixtures |
NAICS | 337215: Showcase, Partition, Shelving, and Locker Manufacturing |
SIC | 2541: Wood Office and Store Fixtures, Partitions, Shelving, and Lockers |
Sales Range | $10 M to 50M |
# of Employees | 85 |
Plant Area |
105,000
ft2
|
Annual Production | 35,000
pieces
|
Production Hrs. Annual | 2,703
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $51,987 | 997,800 |
kWh
|
$0.052 |
Electricity Demand | $32,908 | 4,446 |
kW-mo/yr
|
$7.40 |
Electricity Fees | $7,615 | - |
|
- |
Natural Gas | $9,112 | 1,629 |
MMBtu
|
$5.59 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $35,241 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $33,311 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.8114: Change rate schedules or other changes in utility service | $23,230 | - | - | - | $23,230 | - | |
02 | 2.8121: Apply for tax-free status for energy purchases | $5,913 | - | - | - | $5,913 | - | |
03 | 2.6218: Turn off equipment when not in use | $2,350 | - | - | - | - |
$2,350
-
MMBtu
|
|
04 | 2.7111: Reduce illumination to minimum necessary levels | $1,730 | $110 |
$715
19,620
kWh
|
$1,015
-
kW-mo/yr
|
- | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,188 | $110 |
$488
13,411
kWh
|
$700
-
kW-mo/yr
|
- | - | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $465 | - |
$465
12,800
kWh
|
- | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $200 | $200 |
$140
3,925
kWh
|
$60
-
kW-mo/yr
|
- | - | |
08 | 2.4221: Install compressor air intakes in coolest locations | $165 | $110 |
$165
4,540
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $35,241 | $530 |
$1,973
54,296
kWh
|
$1,775
-
kW-mo/yr
|
$29,143 |
$2,350
-
MMBtu
|
||
TOTAL IMPLEMENTED | $33,311 | $220 |
$1,118
30,751
kWh
|
$700
-
kW-mo/yr
|
$29,143 |
$2,350
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs