| Assessment Year | 2026 |
|---|---|
| Principal Product | Specialty chemicals |
| NAICS | 325998: All Other Miscellaneous Chemical Product and Preparation Manufacturing |
| SIC | 2869: Industrial Organic Chemicals, Not Elsewhere Classified |
| Sales Range | $5 M to 10M |
| # of Employees | 60 |
| Plant Area |
90,000
ft2
|
| Annual Production | 33,865
lb
|
| Production Hrs. Annual | 8,008
hrs
|
| Location (State) | New York |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $240,230 | 3,745,487 |
kWh
|
$0.064 | |
| Electricity Demand | $88,294 | 6,843 |
kW-mo/yr
|
$12.90 | |
| Electricity Fees | $8,681 | - |
|
- | |
| Natural Gas | $143,033 | 22,365 |
MMBtu
|
$6.40 | |
| Waste Disposal Costs | |||||
| Water Usage | $5,800 | 40,000 |
Tgal
|
$0.15 | |
| TOTAL YEARLY COSTS | $486,038 | ||||
| RECOMMENDED SAVINGS* | $411,446 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 3.1161: Eliminate/reduce an operation | $2,057 | - |
$1,224
19,125
kWh
|
$1,355
-
kW-mo/yr
|
- |
$(-521.6)
-
MMBtu
|
- | |
| 02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,223 | - |
$4,223
65,981
kWh
|
- | - | - | - | |
| 03 | 2.8114: Change rate schedules or other changes in utility service | $32,852 | - | - | - | $32,852 | - | - | |
| 04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $35,297 | $15,700 |
$21,204
331,313
kWh
|
$14,093
-
kW-mo/yr
|
- | - | - | |
| 05 | 2.4221: Install compressor air intakes in coolest locations | $2,039 | $943 |
$2,039
31,866
kWh
|
- | - | - | - | |
| 06 | 2.7144: Install spectral reflectors / delamp | $400 | $200 |
$307
4,804
kWh
|
$93
-
kW-mo/yr
|
- | - | - | |
| 07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $829 | $483 |
$829
12,949
kWh
|
- | - | - | - | |
| 08 | 2.4322: Use or replace with energy efficient substitutes | $3,037 | $4,295 |
$1,256
19,622
kWh
|
$347
-
kW-mo/yr
|
- | - | $1,435 | |
| 09 | 2.2511: Insulate bare equipment | $107 | $303 |
$91
1,424
kWh
|
- | - |
$16
-
MMBtu
|
- | |
| 10 | 2.7135: Install occupancy sensors | $231 | $661 |
$231
3,604
kWh
|
- | - | - | - | |
| 11 | 2.7243: Improve air circulation with destratification fans / other methods | $1,849 | $7,665 |
$(-221.8)
(-3,465)
kWh
|
$(-67.7)
-
kW-mo/yr
|
- |
$2,139
-
MMBtu
|
- | |
| 12 | 2.9114: Use solar heat to make electricty | $328,524 | $3,397,400 |
$328,524
3,991,473
kWh
|
- | - | - | - | |
| TOTAL RECOMMENDED | $411,446 | $3,427,650 |
$359,706
4,478,696
kWh
|
$15,820
-
kW-mo/yr
|
$32,852 |
$1,633
-
MMBtu
|
$1,435 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs