Assessment Year | 1983 |
---|---|
Principal Product | CALCIUM CARBIDE |
NAICS |
n/a
|
SIC | 2819: Industrial Inorganic Chemicals, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 70 |
Plant Area |
n/a
|
Annual Production | 36,000
ton
|
Production Hrs. Annual | 8,344
hrs
|
Location (State) | Oklahoma |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $2,199,248 | 121,657,094 |
kWh
|
$0.018 |
Natural Gas | $84,206 | 28,769 |
MMBtu
|
$2.93 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $318,991 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $6,570 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.4221: Install compressor air intakes in coolest locations | $985 | $100 |
$985
47,773
kWh
|
- | - | |
02 | 2.3412: Use waste heat to produce steam to drive a steam turbine-generator | $296,722 | $802,436 |
$518,182
17,584,994
kWh
|
- | $(-221,460.0) | |
03 | 2.4133: Use most efficient type of electric motors | $5,585 | $35,277 |
$5,585
184,349
kWh
|
- | - | |
04 | 2.2422: Use waste heat from hot flue gases to generate steam | $15,699 | $34,357 | - |
$15,699
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $318,991 | $872,170 |
$524,752
17,817,116
kWh
|
$15,699
-
MMBtu
|
$(-221,460.0) | ||
TOTAL IMPLEMENTED | $6,570 | $35,377 |
$6,570
232,122
kWh
|
- | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs