| Assessment Year | 2026 |
|---|---|
| Principal Product | Interior Lighting and Vents for Commercial and Business Jets |
| NAICS | 335122: Commercial, Industrial, and Institutional Electric Lighting Fixture Manufacturing |
| SIC | 3715: Truck Trailers |
| Sales Range | $50 M to 100M |
| # of Employees | 140 |
| Plant Area |
60,000
ft2
|
| Annual Production | 151,673
pieces
|
| Production Hrs. Annual | 2,125
hrs
|
| Location (State) | New York |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $91,892 | 606,400 |
kWh
|
$0.15 |
| Electricity Demand | $45,528 | 3,184 |
kW-mo/yr
|
$14.30 |
| Electricity Fees | $19,248 | - |
|
- |
| Natural Gas | $30,144 | 2,241 |
MMBtu
|
$13.45 |
| Other Gas | $3,220 | 1 |
MMBtu
|
$3,219.64 |
| TOTAL YEARLY COSTS | $190,030 | |||
| RECOMMENDED SAVINGS* | $30,924 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4239: Eliminate or reduce compressed air usage | $400 | - |
$400
2,633
kWh
|
- | - | - | |
| 02 | 2.8121: Apply for tax-free status for energy purchases | $12,170 | $91 | - | - | - | $12,170 | |
| 03 | 2.4322: Use or replace with energy efficient substitutes | $2,563 | $80 |
$2,394
15,750
kWh
|
$1,072
-
kW-mo/yr
|
$(-903.4)
-
MMBtu
|
- | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,169 | $581 |
$797
5,242
kWh
|
$206
-
kW-mo/yr
|
- | $166 | |
| 05 | 2.6211: Conserve energy by efficient use of vending machines | $699 | $561 |
$699
4,598
kWh
|
- | - | - | |
| 06 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $3,991 | $8,000 |
$5,705
37,531
kWh
|
- |
$(-1,713.7)
-
MMBtu
|
- | |
| 07 | 2.7447: Install vinyl strip / high speed / air curtain doors | $963 | $2,290 | - | - |
$963
-
MMBtu
|
- | |
| 08 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $480 | $1,980 | - | - |
$480
-
MMBtu
|
- | |
| 09 | 2.5117: Convert to indirect temperature control system | $8,490 | $75,000 |
$2,823
18,573
kWh
|
$2,652
-
kW-mo/yr
|
$3,014
-
MMBtu
|
- | |
| TOTAL RECOMMENDED | $30,924 | $88,583 |
$12,818
84,327
kWh
|
$3,931
-
kW-mo/yr
|
$1,840
-
MMBtu
|
$12,336 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs