| Assessment Year | 1991 |
|---|---|
| Principal Product | LITHOGRAPHIC PLATES |
| NAICS |
n/a
|
| SIC | 2796: Platemaking and Related Services |
| Sales Range | $10 M to 50M |
| # of Employees | 135 |
| Plant Area |
n/a
|
| Annual Production | 43,700
thousand feet
|
| Production Hrs. Annual | 7,224
hrs
|
| Location (State) | Massachusetts |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $459,802 | 7,057,738 |
kWh
|
$0.065 |
| Natural Gas | $81,399 | 10,136 |
MMBtu
|
$8.03 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $29,951 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $29,951 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7312: Minimize use of outside make-up air for ventilation except when used for economizer cycle | $11,242 | $21,238 | - |
$11,242
-
MMBtu
|
|
| 02 | 2.7261: Install timers and/or thermostats | $6,376 | - |
$6,376
97,890
kWh
|
- | |
| 03 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $5,696 | - |
$11,454
175,850
kWh
|
$(-5,758.0)
-
MMBtu
|
|
| 04 | 2.2443: Re-use or recycle hot or cold process exhaust air | $3,079 | $9,000 |
$76
1,172
kWh
|
$3,003
-
MMBtu
|
|
| 05 | 2.2511: Insulate bare equipment | $3,303 | $856 |
$3,303
50,703
kWh
|
- | |
| 06 | 2.4133: Use most efficient type of electric motors | $255 | $3,020 |
$255
4,103
kWh
|
- | |
| TOTAL RECOMMENDED | $29,951 | $34,114 |
$21,464
329,718
kWh
|
$8,487
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $29,951 | $34,114 |
$21,464
329,718
kWh
|
$8,487
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs