Assessment Year | 2019 |
---|---|
Principal Product | Large Machined Parts |
NAICS | 333612: Speed Changer, Industrial High-Speed Drive, and Gear Manufacturing |
SIC | 3566: Speed Changers, Industrial High-Speed Drives, and Gears |
Sales Range | $10 M to 50M |
# of Employees | 98 |
Plant Area |
178,000
ft2
|
Annual Production | 15,300
units
|
Production Hrs. Annual | 5,760
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $240,591 | 10,892,385 |
kWh
|
$0.022 | |
Electricity Demand | $143,215 | 20,080 |
kW-mo/yr
|
$7.13 | |
Electricity Fees | $21,374 | - |
|
- | |
Natural Gas | $76,743 | 16,435 |
MMBtu
|
$4.67 | |
Waste Disposal Costs | |||||
Water Usage | $4,600 | 1,500,000 |
Tgal
|
$0.003 | |
TOTAL YEARLY COSTS | $486,523 | ||||
RECOMMENDED SAVINGS* | $37,440 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $22,921 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,025 | - |
$1,025
47,205
kWh
|
- | - | - | |
02 | 2.8121: Apply for tax-free status for energy purchases | $3,064 | $264 | - | - | - | $3,064 | |
03 | 2.4322: Use or replace with energy efficient substitutes | $344 | $75 |
$158
7,200
kWh
|
$321
-
kW-mo/yr
|
$(-135.0)
-
MMBtu
|
- | |
04 | 2.8121: Apply for tax-free status for energy purchases | $707 | $264 | - | - | - | $707 | |
05 | 3.1161: Eliminate/reduce an operation | $10,786 | $6,500 |
$(-57.2)
(-2,600)
kWh
|
$(-889.8)
-
kW-mo/yr
|
- | $11,733 | |
06 | 2.7314: Reduce ventilation air | $1,310 | $944 |
$289
13,137
kWh
|
- |
$1,021
-
MMBtu
|
- | |
07 | 2.4221: Install compressor air intakes in coolest locations | $2,923 | $2,832 |
$2,923
132,872
kWh
|
- | - | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $387 | $415 |
$91
4,117
kWh
|
$40
-
kW-mo/yr
|
- | $256 | |
09 | 2.7134: Use photocell controls | $1,305 | $1,645 |
$1,305
59,331
kWh
|
- | - | - | |
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $15,242 | $26,026 |
$6,493
295,190
kWh
|
$4,607
-
kW-mo/yr
|
- | $4,142 | |
11 | 2.6211: Conserve energy by efficient use of vending machines | $347 | $1,404 |
$347
15,768
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $37,440 | $40,369 |
$12,574
572,220
kWh
|
$4,078
-
kW-mo/yr
|
$886
-
MMBtu
|
$19,902 | ||
TOTAL IMPLEMENTED | $22,921 | $31,182 |
$10,812
491,510
kWh
|
$4,647
-
kW-mo/yr
|
- | $7,462 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs