| Assessment Year | 2018 |
|---|---|
| Principal Product | Frozen Desserts |
| NAICS | 311813: Frozen Cakes, Pies, and Other Pastries Manufacturing |
| SIC | 2053: Frozen Bakery Products, Except Bread |
| Sales Range | $10 M to 50M |
| # of Employees | 72 |
| Plant Area |
52,500
ft2
|
| Annual Production | 568,881
units
|
| Production Hrs. Annual | 4,290
hrs
|
| Location (State) | New York |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $117,523 | 2,823,103 |
kWh
|
$0.042 | |
| Electricity Demand | $62,745 | 6,840 |
kW-mo/yr
|
$9.17 | |
| Electricity Fees | $273 | - |
|
- | |
| Natural Gas | $63,590 | 12,816 |
MMBtu
|
$4.96 | |
| Waste Disposal Costs | |||||
| Water Usage | $3,000 | 5,555 |
Tgal
|
$0.54 | |
| TOTAL YEARLY COSTS | $247,131 | ||||
| RECOMMENDED SAVINGS* | $29,527 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $15,365 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,315 | - |
$2,553
60,799
kWh
|
- | - | $(-188.0) | $(-50.0) | |
| 02 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $3,138 | $700 | - |
$3,138
-
kW-mo/yr
|
- | - | - | |
| 03 | 2.4221: Install compressor air intakes in coolest locations | $910 | $651 |
$910
21,676
kWh
|
- | - | - | - | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $272 | $397 |
$129
3,066
kWh
|
$39
-
kW-mo/yr
|
- | $75 | $29 | |
| 05 | 2.1224: Replace boiler | $10,937 | $22,000 | - | - |
$10,937
-
MMBtu
|
- | - | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,640 | $27,679 |
$7,394
176,046
kWh
|
$4,826
-
kW-mo/yr
|
- | $220 | $(-800.0) | |
| 07 | 2.6211: Conserve energy by efficient use of vending machines | $315 | $955 |
$315
7,491
kWh
|
- | - | - | - | |
| TOTAL RECOMMENDED | $29,527 | $52,382 |
$11,301
269,078
kWh
|
$8,003
-
kW-mo/yr
|
$10,937
-
MMBtu
|
$107 | $(-821.0) | ||
| TOTAL IMPLEMENTED | $15,365 | $29,731 |
$7,838
186,603
kWh
|
$8,003
-
kW-mo/yr
|
- | $295 | $(-771.0) | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs