Assessment Year | 2018 |
---|---|
Principal Product | Wood Moulding |
NAICS | 321918: Other Millwork (including Flooring) |
SIC | 2431: Millwork |
Sales Range | $5 M to 10M |
# of Employees | 102 |
Plant Area |
51,000
ft2
|
Annual Production | 10,000
thousand feet
|
Production Hrs. Annual | 4,420
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $114,605 | 2,909,353 |
kWh
|
$0.039 | |
Electricity Demand | $105,253 | 8,872 |
kW-mo/yr
|
$11.86 | |
Electricity Fees | $12,997 | - |
|
- | |
Natural Gas | $77,207 | 11,395 |
MMBtu
|
$6.78 | |
Waste Disposal Costs | |||||
Water Usage | $1,482 | 215 |
Tgal
|
$6.89 | |
TOTAL YEARLY COSTS | $311,544 | ||||
RECOMMENDED SAVINGS* | $18,288 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $13,315 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7224: Reduce space conditioning during non-working hours | $3,533 | - | - | - |
$3,533
-
MMBtu
|
- | - | |
02 | 2.7224: Reduce space conditioning during non-working hours | $773 | - | - | - |
$773
-
MMBtu
|
- | - | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $548 | - |
$548
14,040
kWh
|
- | - | - | - | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $7,502 | $451 |
$7,502
192,358
kWh
|
- | - | - | - | |
05 | 3.1161: Eliminate/reduce an operation | $1,542 | $463 |
$(-49.0)
(-1,260)
kWh
|
$(-128.0)
-
kW-mo/yr
|
- | $580 | $1,139 | |
06 | 2.4235: Remove or close off unneeded compressed air lines | $3,220 | $1,619 |
$2,580
66,148
kWh
|
$640
-
kW-mo/yr
|
- | - | - | |
07 | 2.4221: Install compressor air intakes in coolest locations | $325 | $239 |
$325
8,327
kWh
|
- | - | - | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $266 | $258 |
$113
2,891
kWh
|
$47
-
kW-mo/yr
|
- | $36 | $70 | |
09 | 2.6211: Conserve energy by efficient use of vending machines | $119 | $169 |
$119
3,058
kWh
|
- | - | - | - | |
10 | 2.7134: Use photocell controls | $248 | $403 |
$248
6,363
kWh
|
- | - | - | - | |
11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $212 | $364 |
$123
3,154
kWh
|
$103
-
kW-mo/yr
|
- | $8 | $(-22.0) | |
TOTAL RECOMMENDED | $18,288 | $3,966 |
$11,509
295,079
kWh
|
$662
-
kW-mo/yr
|
$4,306
-
MMBtu
|
$624 | $1,187 | ||
TOTAL IMPLEMENTED | $13,315 | $3,797 |
$10,842
277,981
kWh
|
$662
-
kW-mo/yr
|
- | $624 | $1,187 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs