Assessment Year 2016
Principal Product Fabricated Structural Metal Manufacturing
NAICS 332312: Fabricated Structural Metal Manufacturing
SIC 3444: Sheet Metal Work
Sales Range $10
M
to 50
M
# of Employees 24
Plant Area 52,000
ft2
Annual Production 33,500,000
pieces
Production Hrs. Annual 2,168
hrs
Location (State) New York

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $15,152 354,700
kWh
Electricity Demand $20,183 1,947
kW-mo/yr
Electricity Fees $4,385 -
Natural Gas $2,876 441
MMBtu
TOTAL YEARLY COSTS $42,596
RECOMMENDED SAVINGS* $10,262 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $9,942

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings One-time Revenue or Avoided Cost Savings
01 2.4231: Reduce the pressure of compressed air to the minimum required $320 - $320
7,444
kWh
- - - -
02 2.6212: Turn off equipment during breaks, reduce operating time $1,534 $429 $1,534
35,671
kWh
- - - -
03 3.1161: Eliminate/reduce an operation $2,385 $5,280 $(-32.0)
(-750)
kWh
$(-373.0)
-
kW-mo/yr
- $1,190 $1,600
04 2.7312: Minimize use of outside make-up air for ventilation except when used for economizer cycle $969 $2,348 - - $969
-
MMBtu
- -
05 2.4221: Install compressor air intakes in coolest locations $124 $418 $124
2,879
kWh
- - - -
06 2.7142: Utilize higher efficiency lamps and/or ballasts $4,930 $18,947 $2,020
46,981
kWh
$2,696
-
kW-mo/yr
- $694 $(-480.6)
TOTAL RECOMMENDED $10,262 $27,422 $3,966
92,225
kWh
$2,323
-
kW-mo/yr
$969
-
MMBtu
$1,884 $1,119
TOTAL IMPLEMENTED $9,942 $27,422 $3,646
84,781
kWh
$2,323
-
kW-mo/yr
$969
-
MMBtu
$1,884 $1,119
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings One-time Revenue or Avoided Cost Savings