Assessment Year | 2016 |
---|---|
Principal Product | Capacitors |
NAICS | 334416: Capacitor, Resistor, Coil, Transformer, and Other Inductor Manufacturing |
SIC | 3675: Electronic Capacitors |
Sales Range | $10 M to 50M |
# of Employees | 200 |
Plant Area |
112,000
ft2
|
Annual Production | 7,500,000
pieces
|
Production Hrs. Annual | 6,110
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $213,846 | 5,359,036 |
kWh
|
$0.040 |
Electricity Demand | $59,353 | 9,716 |
kW-mo/yr
|
$6.11 |
Electricity Fees | $254 | - |
|
- |
Natural Gas | $46,466 | 8,980 |
MMBtu
|
$5.17 |
TOTAL YEARLY COSTS | $319,919 | |||
RECOMMENDED SAVINGS* | $14,107 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7111: Reduce illumination to minimum necessary levels | $154 | - |
$110
2,574
kWh
|
$44
-
kW-mo/yr
|
- | - | - | |
02 | 2.4221: Install compressor air intakes in coolest locations | $1,342 | $480 |
$1,342
33,550
kWh
|
- | - | - | - | |
03 | 2.2511: Insulate bare equipment | $296 | $169 | - | - |
$296
-
MMBtu
|
- | - | |
04 | 2.2136: Install / repair insulation on steam lines | $98 | $78 | - | - |
$98
-
MMBtu
|
- | - | |
05 | 2.2414: Use waste heat from hot flue gases to preheat | $3,474 | $3,632 | - | - |
$3,474
-
MMBtu
|
- | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,305 | $1,707 |
$315
7,884
kWh
|
$66
-
kW-mo/yr
|
- | $625 | $299 | |
07 | 3.1161: Eliminate/reduce an operation | $5,577 | $9,195 |
$(-94.0)
(-2,340)
kWh
|
$(-440.0)
-
kW-mo/yr
|
- | $1,300 | $4,811 | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,742 | $6,797 |
$1,221
30,530
kWh
|
$521
-
kW-mo/yr
|
- | - | - | |
09 | 2.6211: Conserve energy by efficient use of vending machines | $119 | $576 |
$119
2,979
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $14,107 | $22,634 |
$3,013
75,177
kWh
|
$191
-
kW-mo/yr
|
$3,868
-
MMBtu
|
$1,925 | $5,110 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs