Assessment Year | 2015 |
---|---|
Principal Product | Heavy Gage Thermoplastic Parts |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 89 |
Plant Area |
84,200
ft2
|
Annual Production | 1,000
units
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $78,595 | 1,233,009 |
kWh
|
$0.064 |
Electricity Demand | $68,890 | 5,875 |
kW-mo/yr
|
$11.73 |
Electricity Fees | $4,278 | - |
|
- |
Natural Gas | $84,871 | 14,913 |
MMBtu
|
$5.69 |
LPG | $5,611 | 182 |
MMBtu
|
$30.83 |
Fuel Oil #2 | $13,143 | 827 |
MMBtu
|
$15.89 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $30,200 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $18,282 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 4.821: Pay bills on time to avoid late fees | $2,820 | - | - | - | - | - | $2,820 | |
02 | 3.7312: Implement a regular maintenance program to reduce emissions from leaky valves and pipe fittings | $3,274 | $1,580 |
$3,274
51,396
kWh
|
- | - | - | - | |
03 | 2.4221: Install compressor air intakes in coolest locations | $964 | $469 |
$964
15,130
kWh
|
- | - | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $383 | $240 |
$234
3,679
kWh
|
$59
-
kW-mo/yr
|
- | $57 | $33 | |
05 | 2.1224: Replace boiler | $11,805 | $10,686 | - | - | - | - | $11,805 | |
06 | 2.6211: Conserve energy by efficient use of vending machines | $218 | $404 |
$218
3,416
kWh
|
- | - | - | - | |
07 | 3.1161: Eliminate/reduce an operation | $956 | $3,709 |
$(-402.0)
(-6,304)
kWh
|
$(-633.0)
-
kW-mo/yr
|
- | $828 | $1,163 | |
08 | 2.2492: Use "heat wheel" or other heat exchanger to cross-exchange building exhaust air with make-up air | $9,780 | $49,000 | - | - |
$9,780
-
MMBtu
|
- | - | |
TOTAL RECOMMENDED | $30,200 | $66,088 |
$4,288
67,317
kWh
|
$(-574.0)
-
kW-mo/yr
|
$9,780
-
MMBtu
|
$885 | $15,821 | ||
TOTAL IMPLEMENTED | $18,282 | $12,506 |
$3,508
55,075
kWh
|
$59
-
kW-mo/yr
|
- | $57 | $14,658 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs