Assessment Year | 2014 |
---|---|
Principal Product | Commercial Printing and Packaging |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2752: Commercial Printing, Lithographic |
Sales Range | $10 M to 50M |
# of Employees | 204 |
Plant Area |
135,000
ft2
|
Annual Production | 27,664,455
pieces
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $290,241 | 5,235,263 |
kWh
|
$0.055 |
Electricity Demand | $204,493 | 12,768 |
kW-mo/yr
|
$16.02 |
Electricity Fees | $7,882 | - |
|
- |
Natural Gas | $25,521 | 3,345 |
MMBtu
|
$7.63 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $16,152 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $767 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.4322: Use or replace with energy efficient substitutes | $5,447 | - |
$1,122
20,250
kWh
|
$4,325
-
kW-mo/yr
|
- | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,882 | - |
$1,882
33,971
kWh
|
- | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,297 | $775 |
$3,297
59,518
kWh
|
- | - | |
04 | 2.7132: Install timers on light switches in little used areas | $1,166 | $632 |
$1,166
21,050
kWh
|
- | - | |
05 | 2.4221: Install compressor air intakes in coolest locations | $2,648 | $2,233 |
$2,648
47,789
kWh
|
- | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $767 | $578 |
$335
6,044
kWh
|
$133
-
kW-mo/yr
|
$299 | |
07 | 2.6211: Conserve energy by efficient use of vending machines | $132 | $399 |
$132
2,388
kWh
|
- | - | |
08 | 3.1161: Eliminate/reduce an operation | $813 | $4,020 |
$(-132.0)
(-2,381)
kWh
|
$(-1,730.0)
-
kW-mo/yr
|
$2,675 | |
TOTAL RECOMMENDED | $16,152 | $8,637 |
$10,450
188,629
kWh
|
$2,728
-
kW-mo/yr
|
$2,974 | ||
TOTAL IMPLEMENTED | $767 | $578 |
$335
6,044
kWh
|
$133
-
kW-mo/yr
|
$299 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs