Assessment Year | 2014 |
---|---|
Principal Product | Disposable Foodservice Packaging |
NAICS | 326150: Urethane and Other Foam Product (except Polystyrene) Manufacturing |
SIC | 3086: Plastics Foam Products |
Sales Range | $100 M to 500M |
# of Employees | 152 |
Plant Area |
221,294
ft2
|
Annual Production | 1,091,000,000
pieces
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,214,803 | 13,820,600 |
kWh
|
$0.088 |
Electricity Demand | $229,819 | 25,906 |
kW-mo/yr
|
$8.87 |
Electricity Fees | $20,298 | - |
|
- |
Natural Gas | $444,870 | 45,574 |
MMBtu
|
$9.76 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $132,114 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $12,372 | - |
$12,372
140,580
kWh
|
- | - | - | - | |
02 | 2.8121: Apply for tax-free status for energy purchases | $11,558 | - | - | - | - | - | $11,558 | |
03 | 2.7224: Reduce space conditioning during non-working hours | $8,530 | - | - | - |
$8,530
-
MMBtu
|
- | - | |
04 | 2.4322: Use or replace with energy efficient substitutes | $2,224 | - |
$1,426
16,200
kWh
|
$798
-
kW-mo/yr
|
- | - | - | |
05 | 2.7122: Disconnect ballasts | $818 | - |
$677
7,694
kWh
|
$141
-
kW-mo/yr
|
- | - | - | |
06 | 2.4221: Install compressor air intakes in coolest locations | $13,361 | $5,132 |
$13,361
151,826
kWh
|
- | - | - | - | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,567 | $1,182 |
$2,567
29,175
kWh
|
- | - | - | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,026 | $2,021 |
$586
6,658
kWh
|
$81
-
kW-mo/yr
|
- | $1,359 | - | |
09 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $73,210 | $87,750 | - | - |
$73,210
-
MMBtu
|
- | - | |
10 | 3.1161: Eliminate/reduce an operation | $4,653 | $5,760 |
$(-156.0)
(-1,776)
kWh
|
$(-1,277.0)
-
kW-mo/yr
|
- | - | $6,086 | |
11 | 2.7135: Install occupancy sensors | $490 | $715 |
$490
5,565
kWh
|
- | - | - | - | |
12 | 2.6211: Conserve energy by efficient use of vending machines | $305 | $507 |
$305
3,468
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $132,114 | $103,067 |
$31,628
359,390
kWh
|
$(-257.0)
-
kW-mo/yr
|
$81,740
-
MMBtu
|
$1,359 | $17,644 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs