Assessment Year | 2014 |
---|---|
Principal Product | Fuel Cells |
NAICS | 334512: Automatic Environmental Control Manufacturing for Residential, Commercial, and Appliance Use |
SIC | 3629: Electrical Industrial Apparatus, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 145 |
Plant Area |
108,500
ft2
|
Annual Production | 918
pieces
|
Production Hrs. Annual | 4,420
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $165,694 | 2,274,166 |
kWh
|
$0.073 |
Electricity Demand | $55,879 | 5,541 |
kW-mo/yr
|
$10.08 |
Electricity Fees | $23,243 | - |
|
- |
Natural Gas | $82,232 | 9,761 |
MMBtu
|
$8.42 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $33,681 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $27,609 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|
01 | 2.4322: Use or replace with energy efficient substitutes | $2,567 | - |
$1,478
20,250
kWh
|
$1,089
-
kW-mo/yr
|
- | |
02 | 2.8121: Apply for tax-free status for energy purchases | $13,052 | - | - | - | $13,052 | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $296 | - |
$296
4,056
kWh
|
- | - | |
04 | 2.7111: Reduce illumination to minimum necessary levels | $695 | $870 |
$695
9,524
kWh
|
- | - | |
05 | 2.7132: Install timers on light switches in little used areas | $533 | $704 |
$533
7,300
kWh
|
- | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $13,728 | $27,708 |
$9,165
125,554
kWh
|
$3,750
-
kW-mo/yr
|
$813 | |
07 | 2.6211: Conserve energy by efficient use of vending machines | $122 | $364 |
$122
1,665
kWh
|
- | - | |
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $296 | $1,020 |
$296
4,056
kWh
|
- | - | |
09 | 2.4221: Install compressor air intakes in coolest locations | $175 | $620 |
$175
2,393
kWh
|
- | - | |
10 | 3.1161: Eliminate/reduce an operation | $2,217 | $8,640 |
$(-168.0)
(-2,304)
kWh
|
$(-2,177.0)
-
kW-mo/yr
|
$4,562 | |
TOTAL RECOMMENDED | $33,681 | $39,926 |
$12,592
172,494
kWh
|
$2,662
-
kW-mo/yr
|
$18,427 | ||
TOTAL IMPLEMENTED | $27,609 | $29,432 |
$9,994
136,910
kWh
|
$3,750
-
kW-mo/yr
|
$13,865 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs