Assessment Year | 2013 |
---|---|
Principal Product | Consumer Products Packaging |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2653: Corrugated and Solid Fiber Boxes |
Sales Range | $100 M to 500M |
# of Employees | 61 |
Plant Area |
240,000
ft2
|
Annual Production | 108,900,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $143,011 | 2,905,175 |
kWh
|
$0.049 |
Electricity Demand | $97,043 | 8,384 |
kW-mo/yr
|
$11.57 |
Electricity Fees | $16,096 | - |
|
- |
Natural Gas | $38,627 | 7,571 |
MMBtu
|
$5.10 |
LPG | $7,869 | 162 |
MMBtu
|
$48.57 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $129,443 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $117,137 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7122: Disconnect ballasts | $1,059 | $320 |
$624
12,480
kWh
|
$278
-
kW-mo/yr
|
- | $157 | |
02 | 3.1161: Eliminate/reduce an operation | $9,433 | $3,600 |
$(-150.0)
(-3,000)
kWh
|
$(-417.0)
-
kW-mo/yr
|
- | $10,000 | |
03 | 2.4221: Install compressor air intakes in coolest locations | $2,037 | $876 |
$2,037
40,725
kWh
|
- | - | - | |
04 | 2.7241: Install outside air damper / economizer on hvac unit | $94,164 | $91,400 | - | - |
$10,164
-
MMBtu
|
$84,000 | |
05 | 2.7135: Install occupancy sensors | $1,088 | $1,424 |
$1,088
21,917
kWh
|
- | - | - | |
06 | 2.6211: Conserve energy by efficient use of vending machines | $171 | $438 |
$171
3,408
kWh
|
- | - | - | |
07 | 2.2437: Recover waste heat from equipment | $20,936 | $61,400 | - | - |
$20,936
-
MMBtu
|
- | |
08 | 2.7122: Disconnect ballasts | $555 | $1,600 |
$343
6,864
kWh
|
$150
-
kW-mo/yr
|
- | $62 | |
TOTAL RECOMMENDED | $129,443 | $161,058 |
$4,113
82,394
kWh
|
$11
-
kW-mo/yr
|
$31,100
-
MMBtu
|
$94,219 | ||
TOTAL IMPLEMENTED | $117,137 | $153,676 |
$2,037
40,725
kWh
|
- |
$31,100
-
MMBtu
|
$84,000 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs