| Assessment Year | 2013 |
|---|---|
| Principal Product | Consumer Products Packaging |
| NAICS | 323111: Commercial Printing (except Screen and Books) |
| SIC | 2653: Corrugated and Solid Fiber Boxes |
| Sales Range | $100 M to 500M |
| # of Employees | 61 |
| Plant Area |
240,000
ft2
|
| Annual Production | 108,900,000
pieces
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | New York |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $143,011 | 2,905,175 |
kWh
|
$0.049 |
| Electricity Demand | $97,043 | 8,384 |
kW-mo/yr
|
$11.57 |
| Electricity Fees | $16,096 | - |
|
- |
| Natural Gas | $38,627 | 7,571 |
MMBtu
|
$5.10 |
| LPG | $7,869 | 162 |
MMBtu
|
$48.57 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $129,443 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $117,137 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7122: Disconnect ballasts | $1,059 | $320 |
$624
12,480
kWh
|
$278
-
kW-mo/yr
|
- | $157 | |
| 02 | 3.1161: Eliminate/reduce an operation | $9,433 | $3,600 |
$(-150.0)
(-3,000)
kWh
|
$(-417.0)
-
kW-mo/yr
|
- | $10,000 | |
| 03 | 2.4221: Install compressor air intakes in coolest locations | $2,037 | $876 |
$2,037
40,725
kWh
|
- | - | - | |
| 04 | 2.7241: Install outside air damper / economizer on hvac unit | $94,164 | $91,400 | - | - |
$10,164
-
MMBtu
|
$84,000 | |
| 05 | 2.7135: Install occupancy sensors | $1,088 | $1,424 |
$1,088
21,917
kWh
|
- | - | - | |
| 06 | 2.6211: Conserve energy by efficient use of vending machines | $171 | $438 |
$171
3,408
kWh
|
- | - | - | |
| 07 | 2.2437: Recover waste heat from equipment | $20,936 | $61,400 | - | - |
$20,936
-
MMBtu
|
- | |
| 08 | 2.7122: Disconnect ballasts | $555 | $1,600 |
$343
6,864
kWh
|
$150
-
kW-mo/yr
|
- | $62 | |
| TOTAL RECOMMENDED | $129,443 | $161,058 |
$4,113
82,394
kWh
|
$11
-
kW-mo/yr
|
$31,100
-
MMBtu
|
$94,219 | ||
| TOTAL IMPLEMENTED | $117,137 | $153,676 |
$2,037
40,725
kWh
|
- |
$31,100
-
MMBtu
|
$84,000 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs