Assessment Year | 2013 |
---|---|
Principal Product | Plastic & Plastic Products |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 126 |
Plant Area |
198,600
ft2
|
Annual Production | 34,700,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $847,265 | 26,481,800 |
kWh
|
$0.032 |
Electricity Demand | $180,851 | 44,328 |
kW-mo/yr
|
$4.08 |
Natural Gas | $37,317 | 4,373 |
MMBtu
|
$8.53 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $39,094 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $24,599 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $24,599 | $3,200 |
$24,599
768,716
kWh
|
- | |
02 | 2.4221: Install compressor air intakes in coolest locations | $6,686 | $1,270 |
$6,686
208,936
kWh
|
- | |
03 | 2.7224: Reduce space conditioning during non-working hours | $461 | $83 | - |
$461
-
MMBtu
|
|
04 | 2.7135: Install occupancy sensors | $1,051 | $326 |
$1,051
32,850
kWh
|
- | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $6,297 | $21,467 |
$6,297
196,224
kWh
|
- | |
TOTAL RECOMMENDED | $39,094 | $26,346 |
$38,633
1,206,726
kWh
|
$461
-
MMBtu
|
||
TOTAL IMPLEMENTED | $24,599 | $3,200 |
$24,599
768,716
kWh
|
- |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs