Assessment Year | 2011 |
---|---|
Principal Product | Recycled Commodities |
NAICS | 562920: Materials Recovery Facilities |
SIC | 4953: Refuse Systems |
Sales Range | $1 M to 5M |
# of Employees | 41 |
Plant Area |
68,000
ft2
|
Annual Production | 40,000
ton
|
Production Hrs. Annual | 4,680
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $93,898 | 1,363,291 |
kWh
|
$0.069 |
Electricity Demand | $53,595 | 6,041 |
kW-mo/yr
|
$8.87 |
Electricity Fees | $11,409 | - |
|
- |
Natural Gas | $55,571 | 3,330 |
MMBtu
|
$16.69 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $32,588 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $28,203 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,744 | - |
$1,744
25,272
kWh
|
- | - | - | - | |
02 | 2.8121: Apply for tax-free status for energy purchases | $2,054 | - | - | - | - | - | $2,054 | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $323 | $97 |
$323
4,680
kWh
|
- | - | - | - | |
04 | 2.4221: Install compressor air intakes in coolest locations | $1,550 | $920 |
$1,550
22,464
kWh
|
- | - | - | - | |
05 | 2.2442: Preheat combustion air with waste heat | $16,557 | $21,257 | - | - | - |
$16,557
-
MMBtu
|
- | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,579 | $21,668 |
$7,202
104,364
kWh
|
$2,377
-
kW-mo/yr
|
- | - | - | |
07 | 2.6211: Conserve energy by efficient use of vending machines | $139 | $287 |
$139
2,021
kWh
|
- | - | - | - | |
08 | 2.3212: Optimize plant power factor | $642 | $4,591 | - | - | $642 | - | - | |
TOTAL RECOMMENDED | $32,588 | $48,820 |
$10,958
158,801
kWh
|
$2,377
-
kW-mo/yr
|
$642 |
$16,557
-
MMBtu
|
$2,054 | ||
TOTAL IMPLEMENTED | $28,203 | $43,022 |
$9,269
134,316
kWh
|
$2,377
-
kW-mo/yr
|
- |
$16,557
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs