Assessment Year 2010
Principal Product Automotive tire pressure sensors, Remote keyless entry devices
NAICS 336320: Motor Vehicle Electrical and Electronic Equipment Manufacturing
SIC 3714: Motor Vehicle Parts and Accessories
Sales Range $100
M
to 500
M
# of Employees 200
Plant Area 72,051
ft2
Annual Production 21,108,010
pieces
Production Hrs. Annual 4,000
hrs
Location (State) New York

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $466,183 5,261,529
kWh
Electricity Demand $97,541 11,628
kW-mo/yr
Electricity Fees $5,387 -
Natural Gas $68,727 6,501
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $34,756 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $27,702

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings One-time Revenue or Avoided Cost Savings
01 2.6231: Utilize controls to operate equipment only when needed $13,013 - $13,013
143,000
kWh
- - -
02 2.4231: Reduce the pressure of compressed air to the minimum required $3,573 - $2,559
28,128
kWh
$1,014
-
kW-mo/yr
- -
03 4.821: Pay bills on time to avoid late fees $1,552 - - - - $1,552
04 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $7,383 $578 $6,537
71,382
kWh
$846
-
kW-mo/yr
- -
05 2.2437: Recover waste heat from equipment $3,787 $964 - - $3,787
-
MMBtu
-
06 2.7135: Install occupancy sensors $1,653 $1,236 $1,653
18,168
kWh
- - -
07 2.6211: Conserve energy by efficient use of vending machines $528 $714 $528
5,798
kWh
- - -
08 2.7142: Utilize higher efficiency lamps and/or ballasts $3,267 $8,373 $2,545
27,960
kWh
$722
-
kW-mo/yr
- -
TOTAL RECOMMENDED $34,756 $11,865 $26,835
294,436
kWh
$2,582
-
kW-mo/yr
$3,787
-
MMBtu
$1,552
TOTAL IMPLEMENTED $27,702 $2,528 $24,290
266,476
kWh
$1,860
-
kW-mo/yr
- $1,552
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs