Assessment Year | 2009 |
---|---|
Principal Product | Tire Cord |
NAICS | 314994: Rope, Cordage, Twine, Tire Cord, and Tire Fabric Mills |
SIC | 2269: Finishers of Textiles, Not elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 152 |
Plant Area |
396,000
ft2
|
Annual Production | 16,950,000
lb
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,550,142 | 20,345,288 |
kWh
|
$0.076 |
Electricity Demand | $184,491 | 37,579 |
kW-mo/yr
|
$4.91 |
Electricity Fees | $118,783 | - |
|
- |
Natural Gas | $770,310 | 70,331 |
MMBtu
|
$10.95 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $106,693 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $96,934 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $25,359 | - |
$22,614
279,180
kWh
|
$2,745
-
kW-mo/yr
|
- | |
02 | 2.4314: Use synthetic lubricant | $8,358 | - |
$7,445
91,920
kWh
|
$913
-
kW-mo/yr
|
- | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $8,050 | - |
$7,181
88,640
kWh
|
$869
-
kW-mo/yr
|
- | |
04 | 2.4221: Install compressor air intakes in coolest locations | $4,305 | $528 |
$3,839
47,400
kWh
|
$466
-
kW-mo/yr
|
- | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,615 | $410 |
$3,222
39,780
kWh
|
$393
-
kW-mo/yr
|
- | |
06 | 2.7135: Install occupancy sensors | $44,212 | $7,299 |
$44,212
545,824
kWh
|
- | - | |
07 | 2.2511: Insulate bare equipment | $1,289 | $1,820 |
$1,289
15,910
kWh
|
- | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,049 | $6,721 |
$3,593
44,376
kWh
|
$456
-
kW-mo/yr
|
- | |
09 | 2.6211: Conserve energy by efficient use of vending machines | $112 | $271 |
$112
1,379
kWh
|
- | - | |
10 | 2.3212: Optimize plant power factor | $7,344 | $28,458 | - | - | $7,344 | |
TOTAL RECOMMENDED | $106,693 | $45,507 |
$93,507
1,154,409
kWh
|
$5,842
-
kW-mo/yr
|
$7,344 | ||
TOTAL IMPLEMENTED | $96,934 | $43,416 |
$84,661
1,045,200
kWh
|
$4,929
-
kW-mo/yr
|
$7,344 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs