Assessment Year | 2009 |
---|---|
Principal Product | Point of Sale Hardware |
NAICS | 333318: Other Commercial and Service Industry Machinery Manufacturing |
SIC | 3578: Calculating and Accounting Machines, Except Electronic Computers |
Sales Range | $100 M to 500M |
# of Employees | 370 |
Plant Area |
208,700
ft2
|
Annual Production | 20,233
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $257,700 | 2,814,487 |
kWh
|
$0.092 |
Electricity Demand | $130,034 | 8,586 |
kW-mo/yr
|
$15.14 |
Electricity Fees | $4,919 | - |
|
- |
Natural Gas | $11,120 | 1,000 |
MMBtu
|
$11.12 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $32,266 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $3,897 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.8114: Change rate schedules or other changes in utility service | $11,264 | - | - | - | - | - | $11,264 | |
02 | 2.8114: Change rate schedules or other changes in utility service | $2,328 | - | - | - | - | - | $2,328 | |
03 | 2.4314: Use synthetic lubricant | $545 | - |
$257
2,789
kWh
|
$288
-
kW-mo/yr
|
- | - | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $498 | - |
$44
482
kWh
|
$454
-
kW-mo/yr
|
- | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,346 | $400 |
$120
1,308
kWh
|
$1,226
-
kW-mo/yr
|
- | - | - | |
06 | 2.4221: Install compressor air intakes in coolest locations | $316 | $204 |
$28
304
kWh
|
$288
-
kW-mo/yr
|
- | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $341 | $268 |
$185
2,015
kWh
|
$45
-
kW-mo/yr
|
- | $20 | $91 | |
08 | 2.7135: Install occupancy sensors | $534 | $595 |
$534
5,802
kWh
|
- | - | - | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $13,444 | $21,840 |
$11,173
121,446
kWh
|
$2,271
-
kW-mo/yr
|
- | - | - | |
10 | 2.6211: Conserve energy by efficient use of vending machines | $458 | $720 |
$458
4,976
kWh
|
- | - | - | - | |
11 | 2.3212: Optimize plant power factor | $1,192 | $7,749 | - | - | $1,192 | - | - | |
TOTAL RECOMMENDED | $32,266 | $31,776 |
$12,799
139,122
kWh
|
$4,572
-
kW-mo/yr
|
$1,192 | $20 | $13,683 | ||
TOTAL IMPLEMENTED | $3,897 | $8,353 |
$449
4,883
kWh
|
$2,256
-
kW-mo/yr
|
$1,192 | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs