Assessment Year 2008
Principal Product Healthy and Organic Snacks
NAICS 311919: Other Snack Food Manufacturing
SIC 2096: Potato Chips, Corn Chips, and Similar Snacks
Sales Range $50
M
to 100
M
# of Employees 200
Plant Area 350,000
ft2
Annual Production 22,000,000
lb
Production Hrs. Annual 6,000
hrs
Location (State) New York

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $437,900 5,927,727
kWh
Electricity Demand $146,528 17,001
kW-mo/yr
Electricity Fees $23,062 -
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $152,651 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $65,237

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Administrative Changes Savings
01 4.812: Apply for investment incentives $67,532 - - - $67,532
02 2.3131: Reschedule plant operations or reduce load to avoid peaks $21,466 - - $21,466
-
kW-mo/yr
-
03 2.3137: Use power during off-peak periods $19,882 - - - $19,882
04 2.4231: Reduce the pressure of compressed air to the minimum required $8,013 - $6,482
88,800
kWh
$1,531
-
kW-mo/yr
-
05 2.4221: Install compressor air intakes in coolest locations $4,164 $173 $3,373
46,200
kWh
$791
-
kW-mo/yr
-
06 2.7135: Install occupancy sensors $2,414 $535 $2,414
33,075
kWh
- -
07 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $11,418 $1,650 $9,242
126,600
kWh
$2,176
-
kW-mo/yr
-
08 2.7142: Utilize higher efficiency lamps and/or ballasts $17,762 $31,086 $14,365
196,800
kWh
$3,397
-
kW-mo/yr
-
TOTAL RECOMMENDED $152,651 $33,444 $35,876
491,475
kWh
$29,361
-
kW-mo/yr
$87,414
TOTAL IMPLEMENTED $65,237 $33,444 $35,876
491,475
kWh
$29,361
-
kW-mo/yr
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs